Installing the boiler
Electrical connections
Outside temperature sensor
For fitting the wireless outside temperature sensor
(wireless accessory):
Wireless base station installation and service
instructions
Fitting location for outside temperature sensor
■
North or north-western wall, 2 to 2.5 m above ground
level; in multi storey buildings, in the upper half of the
second floor
■
Not above windows, doors or vents
Connecting the Vitoconnect 100, type OPTO1 connecting cable (accessories)
3.
Fig. 13
External demand via switching contact
Connection options:
EA1 extension (accessory, see separate installation
■
instructions)
■
Plug
lH
When the contact is closed, burner operation is load-
dependent. The boiler water is heated to the value set
in parameter "9b" in the "General" group. The boiler
water temperature is limited by this set value and the
electronic maximum limit (parameter "06" in the
"Boiler" group).
20
(cont.)
!
2.
1.
Not immediately below balconies or gutters
■
■
Never render over
Outside temperature sensor connection
2-core lead, length max. 35 m with a cross-section of
2
1.5 mm
Installing the Vitoconnect 100
Vitoconnect 100 installation and commissioning
instructions
!
Please note
Live contacts lead to short circuits or phase fail-
ure.
The external connection must be potential-free
and meet the requirements of protection class II.