Outside Temperature Sensor; Floating Switching Contact Connection - Viessmann Vitovalor PT2 Installation And Service Instructions For Contractors

Fuel cell based micro chp unit with integral gas condensing boiler and adjacent cylinder module natural gas version
Table of Contents

Advertisement

Electrical connections

Outside temperature sensor

Fitting location for outside temperature sensor
North or north-westerly wall, 2 to 2.5 m above
ground level; in multi storey buildings, in the upper
half of the second floor
Not above windows, doors or vents
Not immediately below balconies or gutters
Never render over.

Floating switching contact connection

Connection at plug
lH
One of the following functions can be connected:
External demand
External blocking
DHW circulation pump external demand (pushbutton
function, pump runs for 5 min). Cannot be connected
with Vitodens 222-W.
Room temperature controller (room thermostat)
For room temperature-dependent operating mode
A
1 L
N
?
lH
Fig. 39
A
Floating contact
(cont.)
!
Outside temperature sensor connection
Connect outside temperature sensor on plug
heat management unit. See page 42.
2-core lead, length up to 35 m with a cross-section
2
of 1.5 mm
Assigning functions in the commissioning assis-
tant
See commissioning assistant in "Commissioning".
Installation sequence