Electrical connections
Outside temperature sensor
Fitting location for outside temperature sensor
■
North or north-westerly wall, 2 to 2.5 m above
ground level; in multi storey buildings, in the upper
half of the second floor
Not above windows, doors or vents
■
Not immediately below balconies or gutters
■
■
Never render over.
Floating switching contact connection
Connection at plug
lH
One of the following functions can be connected:
External demand
■
■
External blocking
■
DHW circulation pump external demand (pushbutton
function, pump runs for 5 min). Cannot be connected
with Vitodens 222-W.
■
Room temperature controller (room thermostat)
For room temperature-dependent operating mode
A
1 L
N
?
lH
Fig. 39
A
Floating contact
(cont.)
!
Outside temperature sensor connection
Connect outside temperature sensor on plug
heat management unit. See page 42.
2-core lead, length up to 35 m with a cross-section
2
of 1.5 mm
Assigning functions in the commissioning assis-
tant
See commissioning assistant in "Commissioning".