Function Sequence And Possible Faults - Viessmann Vitodens 222-F Installation And Service Instructions For Contractors

Gas condensing storage combi boiler natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance

Function sequence and possible faults

Control unit issues a heat
demand
Yes
Fan starts
Yes
Ignition
Yes
Gas train opens
Yes
Ionisation current builds
Symbol
A
Yes
Burner in operation
Yes
Automatic calibration of
the combustion controller
For further details regarding faults, see page 89.
38
Display
No
No
Fan starts 4 times for
approx. 50 s, followed by
fault F9
No
Fault 81/EE
No
Fault 80/EE
No
Fault 82/EE
No
Shuts down below the set
boiler water temperature and
restarts immediately.
Fault E3
No
Fault Eb
Fault 85/E1/E7/E9/EA
Action
Increase set value and en-
sure heat is drawn off.
Check the fan, fan connect-
ing cables, power to the fan
and fan control.
Check ignition module (con-
trol voltage 230 V across
plugs "X2.1" and "X2.2").
Check the gas supply.
Check the gas train (control
voltage 230 V
); check the
gas supply pressure.
Check setting for ionisation
electrode.
Purge the gas line.
Check the flue system for
tightness (flue gas recircula-
tion); check the gas flow
pressure.
Ensure adequate heat trans-
fer. Press reset button R.
Check gap between ionisa-
tion electrode and burner
gauze assembly. Check allo-
cation of gas type (coding
address 82, gas train set-
ting). Check flue system; re-
move flue gas recirculation if
required. Press reset button
R.
See chapter "Fault messag-
es"