Viessmann Vitodens 222-F Installation And Service Instructions For Contractors page 94

Gas condensing storage combi boiler natural gas and lpg version
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Fault code dis-
System characteristics
played
B7
Burner blocked
B8
Burner in a fault state
BA
Mixer regulates to 20 °C flow
temperature.
BB
Mixer regulates to 20 °C flow
temperature.
BC
Control mode without remote
control
BD
Control mode without remote
control
BE
Control mode without remote
control
BF
Control mode
C1
Control mode
C3
Control mode
C4
Control mode
C5
Control mode, max. pump
speed
CD
Control mode
CF
Control mode
D3
Burner in a fault state or
blocked
D4
Control mode
Burner is operating with a
limited modulation range.
D5
Burner in a fault state
94
Cause
Boiler coding card fault
Lead break, flue gas tem-
perature sensor
Communication error, ex-
tension kit for heating cir-
cuit 2 (with mixer)
Communication error, ex-
tension kit for heating cir-
cuit 3 (with mixer)
Communication error,
Vitotrol remote control,
heating circuit 1 (without
mixer)
Communication error,
Vitotrol remote control,
heating circuit 2 (with mix-
er)
Communication error,
Vitotrol remote control,
heating circuit 3 (with mix-
er)
Incorrect LON communi-
cation module
Communication error, EA1
extension
Communication error,
AM1 extension
Communication error,
OpenTherm extension
Communication error, in-
ternal variable speed
pump
Communication error,
Vitocom 100 (KM-BUS)
Communication error,
communication module
Communication error, fan
unit.
No air flow detected in fan
unit.
Fan blocked
Measures
Plug in boiler coding card or re-
place if faulty
Check flue gas temperature sensor
and connecting lead.
Check extension kit connections
and assignment.
Check extension kit connections
and assignment.
Check connections, lead, parame-
ter "A0" and remote control set-
tings (see page 141).
For wireless remote control units:
check connection; place remote
control close to the boiler.
Check connections, lead, parame-
ter "A0" and remote control set-
tings (see page 141).
For wireless remote control units:
check connection; place remote
control close to the boiler.
Check connections, lead, parame-
ter "A0" and remote control set-
tings (see page 141).
For wireless remote control units:
check connection; place remote
control close to the boiler.
Replace LON communication mod-
ule
Check connections
Check connections
Check OpenTherm extension
Check setting of parameter "30"
Check connections, Vitocom 100
and parameter "95"
Replace communication module
Check the connecting cable to the
fan unit. Press reset button R.
If the fault recurs, replace the fan
unit.
Check the mass flow sensor at the
fan unit. Check the flue system for
flue gas back pressure.
Press reset button R. Check fan
impeller movement. If necessary,
replace fan.