Play Message After; Periodic Report; Address Book; Voice Messages - FireClass FC500 Pc Programming Manual

Addressable fire control panels
Table of Contents

Advertisement

the previous event, up to the time all telephone
calls succeed, or at most, for the numbers of call
attempts programmed. If the Call all telemonitoring
numbers options is disabled, the PSTN interface
will interrupt the call as soon as it succeeds.
Call all voice messages: If the Call all voice
messages numbers option is enabled (default
setting), the PSTN interface calls all programmed
numbers for the previous event, until all phone
calls succeed according to the numbers of call
attempts programmed. If the Call all voice
messages is disabled, the PSTN interface will
interrupt the calls as soon as one is successful.

Play message after

The section Play message after sets the condition for the
voice message playback.
Dialling: Message playback occurs as soon as
the telephone number is dialled.
Voice: Message playback occurs when the PSTN
interface detects a voice answer.
Delay: Message playback occurs when the
programmed delay elapses after the telephone
number is dialled. You can set the delay from 0 to
99 seconds, with 1 second steps. The default
setting is 0 seconds.

Periodic report

The section Periodic report sets the parameters
corresponding to the Period test as described below.
Date and time first test: Set the date and time for
the first Periodic test.
Period: Set the interval between two periodic
tests. You can set the interval from 1 up to 25
hours, in steps of 1 hour. The default setting is 24
hours.
Note: The Periodic test event is not recorded in the Events
log.

Address book

The section Address book programs the telephone
numbers that you can use to send:
Voice messages: Dialler function and
telemonitoring data occur when the events are
recognised by the panel.
In the case of Telemonitoring, select:
The type of protocol (SIA, ADEMCO Contact ID)
and customer code.
Phone numbers are only for alarms, faults and numbers of
general use.

Voice messages

In the section Voice messages, parameters relating to
voice messages are programmed, as described below.
(1-7) Messages: You cannot edit messages 1 to 7.
(8-32) Messages: You can assign a maximum 20
characters description to messages 8-32.
Table 9: Icons in the Voice messages section
Icon
Listen to a present message.
Stop the message playback.
Delete the selected message.
You can record a voice message via the
computer microphone for a maximum of 6
seconds; record the header message for a
maximum of 12 seconds.
Imports an audio file (mp3, wav) for use in a
voice message (maximum length is 6 seconds).
Note: A USB memory stick is the only way to download
audio files from the panel.

IP Interface

The IP interface section activates after the FC500IP
module is enabled in the General options screen. See
Figure
13. The IP module programming has three
sections: Options, Address book and Advanced.
Options
DHCP: Select this option if you want to use a
dynamic address for the IP module you are
programming.
IP static: Select this option if you want to assign a
static IP address to the IP module you are
programming and set the following parameters:
 IP address: Enter the IP address assigned to
the IP module. The network administrator
provides this information. The default setting is
192.168.0.101.
 Subnet mask: This must be the same as the
subnet mask for the local network. There is only
one valid subnet mask for each local network. All
nodes on the same subnet use the same subnet
mask. The network administrator provides this
information. The default setting is 255.255.0.0.

Ethernet speed

Use this section to set the parameters corresponding to
the Ethernet interface of the IP module. The default
selection is Auto setting.
Auto: If you enable the option, the IP module
takes the speed and duplex values from the
network. If this option is disabled, the speed and
duplex values must be set as described below.