Mitsubishi Electric 800 Series Instruction Manual page 93

Compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Fault
Protective
function
Alarm,
Warning, Error
message
Surrounding air temperature
Surrounding air humidity
Storage temperature
Ambience
Altitude/vibration
*1
Available when a Vector control compatible option (FR-A8AP E kit) is installed.
*2
Available only for the standard model.
*3
Available only for the Ethernet model and the safety communication model.
*4
Not activated in the inverter in the initial state.
*5
Applicable to conditions for a short time, for example, in transit.
*6
For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
92
4. Specifications
4.2 Common specifications
Overcurrent trip during acceleration, Overcurrent trip during constant speed, Overcurrent trip during
deceleration or stop, Regenerative overvoltage trip during acceleration, Regenerative overvoltage trip
during constant speed, Regenerative overvoltage trip during deceleration or stop, Inverter overload
trip (electronic thermal relay function), Motor overload trip (electronic thermal relay function), Heat
sink overheat, Undervoltage, Input phase loss, Stall prevention stop, Loss of synchronism detection
Upper limit fault detection, Lower limit fault detection, Brake transistor fault, Output side earth (ground)
fault overcurrent, Output short circuit, Output phase loss, External thermal relay operation, Option
fault, Communication option fault, Parameter storage device fault, PU disconnection, Retry count
excess, CPU fault, Abnormal output current detection, Inrush current limit circuit fault, USB
communication fault, Analog input fault, Safety circuit fault, Overspeed occurrence
*1*4
excess detection
communication fault, Opposite rotation deceleration fault
by the PLC function, Board combination mismatch
Fan alarm, stall prevention (overcurrent), stall prevention (overvoltage), regenerative brake pre-
*4
alarm
, electronic thermal relay function pre-alarm, PU stop, maintenance timer alarm, parameter
write error, operation panel lock
communication fault
-10°C to +60°C (The rated current must be reduced at a temperature above 50°C.)
95% RH or less (non-condensing) (With circuit board coating (conforming to IEC 60721-3-3 3C2))
90% RH or less (non-condensing) (Without circuit board coating)
*5
-40°C to +70°C
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
*6
Maximum 2000 m
*1*4
, Signal loss detection
, Brake sequence fault
*4
, Password locked, speed limit indication, safety stop, Ethernet
*3
*3
, duplicate IP address
, IP address fault
2
, 5.9 m/s
or less at 10 to 55 Hz in X, Y, and Z directions
*4
, Speed deviation
*4
, PID signal fault, Ethernet
*4
, Internal circuit fault, User definition error
*3
, incorrect parameter setting
*4
,