Countermeasures against deterioration of the 600
V class motor insulation
In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the motor terminals. Especially in a
600 V class motor, the surge voltage may deteriorate the insulation.
When the 600 V class motor is driven by the inverter, consider the following countermeasures:
200
150
100%
0
10
20 30
Surge voltage at a motor terminal by motor wiring length (reference)
Countermeasures
Inverter duty motor
Select an inverter duty motor. Many motor manufacturers sell motors with insulation systems designed to withstand the stress
imposed by PWM inverters
AC reactor
• For added protection, install an AC reactor on the inverter output