General Ventilation Connections; Ventilation Flow; Adjusting Ventilation; Dimension And Ventilation Connections - Nibe GV-HR 130 Series Installer Manual

Ventilation heat exchanger
Hide thumbs Also See for GV-HR 130 Series:
Table of Contents

Advertisement

General ventilation
connections
• Ventilation installation must be carried out in accord-
ance with current norms and directives.
• Connections must be made via flexible hoses, which
should be installed so that they are easy to replace.
• Provision must be made for inspection and cleaning
of the duct.
• Make sure that there are no reductions of cross-sec-
tional area in the form of creases, tight bends, etc.,
since this will reduce the ventilation capacity.
• The air duct system must be a minimum of air tight-
ness class B.
• To prevent fan noise being transferred to the ventila-
tion devices, silencers should be installed in the duct
system. In the event of ventilation devices in noise-
sensitive rooms, silencers must be installed.
• The extract air and outdoor air ducts are insulated us-
ing diffusion-proof material (at least PE30 or equival-
ent) along their entire lengths.
• Ensure that the condensation insulation is fully sealed
at any joints and/or at lead-in nipples, silencers, roof
cowls or similar.
• The air must be routed to the outdoor air duct through
an outer wall grille in the facade. The outer wall grille
must be installed so that it is protected from the
weather and must be designed so that no rainwater
and/or snow can penetrate the facade or follow the
air into the duct.
• When positioning the outdoor air and extract air
hood/grille, bear in mind that the two air flows must
not short circuit to prevent the extract air from being
drawn into GV-HR 130 again.
• A duct in a masonry chimney stack must not be used
for extract air or outdoor air.
NOTE
To ensure a sealed connection to GV-HR 130,
nipples must be used when connecting the air
ducts.
EXHAUST AIR DUCT /KITCHEN FAN
Exhaust air duct (kitchen fan) must not be connected to
GV-HR 130.
NIBE GV-HR 130
To prevent food vapour being transferred to GV-HR 130
the distance between the kitchen fan and the exhaust
air device must be considered. The distance should not
be less than 1.5 m, but this can vary between different
installations.
Always use a kitchen fan when cooking.

Ventilation flow

Connect GV-HR 130 so that all the exhaust air, except
kitchen duct air (kitchen fan), passes through the heat
exchanger (EP26) in the product.
The ventilation flow must comply with the applicable
national standards.
The supply air flow must be lower than the exhaust air
flow to prevent over pressure in the house.
Set the ventilation capacity in the ventilation heat ex-
changer's menu system (Service menu 10-15).

Adjusting ventilation

To obtain the necessary air exchange in every room of
the house, the exhaust air valve and the supply air inlet
as well as the fans in the ventilation heat exchanger
must be correctly positioned and adjusted.
Immediately after installation adjust the ventilation so
that it is set according to the projected value of the
house.
Incorrect adjustment of the ventilation may lead to re-
duced installation efficiency and thus poorer operating
economy, and may cause moisture damage in the
building
Dimension and
ventilation
connections
Exhaust air
Supply air
Outdoor air
Extract air
Chapter 4 | Pipe and ventilation connections
Ø125
Ø125
120
120
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gv-hr 130-150Gv-hr 130-250

Table of Contents