The termination network below required at each end of each Bus Ph-segment.
ExV is supplied by the Node at end of the Bus Segment
The specifications of the components are:
2.3.3
The end node in each Ph-segment applies 5 V bus excitation power to the Termination
network via the Excitation pair (ExV+ and GND) used in the Type 3 Physical layer
specification.
6.5.3

Data on RS485 serial communication module cable

Type:
Shield:
Length:
Temp:
Impedance:
Capacitance:
Example:
72
c) Vim - the common mode voltage between any pair of RS485 chips may not exceed
10 V.
d) A physical earth connection between all RS485 circuits will reduce noise.
Bus segment termination network
ExV+
Signal B
Signal A
DGND
ExV is supplied by the Node at end of the Bus Segment
IEC03000112 V1 EN-US
Figure 52: RS-485 bus segment termination
a) Ru
+ 5 V to Signal B
b) Rt
Signal B to Signal A
c) Rd
Signal A to GND
Bus power distribution
Twisted-pair S-STP (Screened – Screened Twisted Pair)
Individual foil for each pair with overall copper braid
Maximum 1200 m (3000 ft) from one system earth to the next system earth (includes
length from platform point to system earth on both sides)
According to application
120 W
Less than or equal to 42 pF/m
Belden 9841,Alpha wire 6412, 6413
Ru = 390 ohm
1/4 W, 2%
Rt = 220 ohm
1/4 W, 2%
Rd = 390 ohm
1/4 W, 2%
en03000112.vsd
= 390 W, 0.25 W ±2.5%
= 220 W, 0.25 W ±2.5%
= 390 W, 0.25 W ±2.5%
1MRK514024-UEN A
SEMOD176342-280 v2
Installation manual