ABB RELION 670 Series Installation Manual page 69

Version 2.1 iec
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK514024-UEN A
IED
VOLTAGE MEASURE (U)
CURRENT MEASURE (U)
VOLTAGE MEASURE (U)
CURRENT MEASURE (U)
IEC11000209 V1 EN-US
Figure 42: Separate analog inputs for stator STTIPHIZ and rotor ROTIPHIZ
2.
It is possible to use a mixed connection that requires only two IED voltage channels for
both ROTIPHIZ and STTIPHIZ. REX060 outputs are connected in series. This connection is
not recommended and can be used only in applications where it is prove the possibility to
use it. the use of this connection leads to reduced performances of both ROTIPHIZ and
STTIPHIZ.
IED
VOLTAGE MEASURE (U)
CURRENT MEASURE (U)
IEC11000210 V1 EN-US
Figure 43: Connection to IED with two analogue voltage inputs
Some settings are required for the analog voltage inputs. Set the voltage ratio for the inputs
to 1/1, for example, VTSecx = 100 V VTPrimx = 0.1 kV
The analog inputs are linked to a pre-processor block in the Signal Matrix Tool. This pre-
processor block must have the same cycle time, 8 ms, as the function blocks for STTIPHIZ and
ROTIPHIZ.
Installation manual
protection
REX060
X61
8
9
STATOR MODULE SIM
10
11
X81
8
9
ROTOR MODULE RIM
10
11
IEC11000209-1-en.vsd
REX060
X61
8
9
STATOR MODULE SIM
10
11
X81
8
9
ROTOR MODULE RIM
10
11
IEC11000210-1-en.vsd
Section 6
Connecting
63