1MRK514024-UEN A
Table 15:
No
1
2
3
4
5
Connect each signal connector terminal of screw compression type with one 0.5 to 2.5 mm
(AWG 24 - AWG 14) wire or with two 0.5 to 1.0 mm
Protective conductor terminal must be connected to the cubicle or station protective earthing
system. Electrical codes and standards require that protective earth cables are green/yellow
conductors with a cross section area of at least 2.5 mm
properly connected to the station earthing system. Use a conductor with a core cross section
area of at least 4 mm
REX061 Capacitor unit connections
Table 16:
No
1
2
3
4
5
6
7
8
9
10
Table 17:
No
1
2
3
X1 connector. Connect each signal connector terminal of screw compression type with one
0.14 to 6 mm
X2 connector. Connect each signal connector terminal of screw compression type with one 0.5
to 2.5 mm
Protective conductor terminal must be connected to the cubicle or station protective earthing
system. Electrical codes and standards require that protective earth cables are green/yellow
conductors with a cross section area of at least 2.5 mm
Installation manual
Rotor injection connection X82
Injection (same as 3)
Injection, inside shunt resistor
Injection (same as 1)
Injection return (same as 5)
Injection return (same as 4)
2
(AWG 12).
Injection and rotor connection X1
Rotor positive pole
-
Positive pole
-
Negative pole
-
Rotor negative pole
-
Rotor injection
Injection earth. Internally connected to chassis and PE
Measurment connector X2
Rotor + voltage divided by 1 000
Earth
Rotor - voltage divided by 1 000
2
(AWG 35 - AWG 3) wire or with two 0.14 to 1.5 mm
2
(AWG 24 - AWG 14) wire or with two 0.5 to 1.0 mm
Signal
2
(AWG 24 - AWG 18) wires.
2
(AWG 14). The cubicle must be
Signal
Signal
2
(AWG 35 - AWG 15) wires.
2
(AWG 24 - AWG 18) wires.
2
(AWG 14). The cubicle must be
Section 6
Connecting
2
61