5.3.3.3

How to reach the rear side of the IED

The IED can be equipped with a rear protection cover recommended to be used with this type
of mounting. See figure 6.
To reach the rear side of the IED, a free space of 80 mm is required on the unhinged side.
IEC06000135 V3 EN-US
Figure 6:
PosNo
1
2
3
5.3.4

Side-by-side 19" rack mounting

5.3.4.1

Overview

IED case size 1/2 x 19" or 3/4 x 19" and RHGS cases can be mounted side-by-side up to a
maximum size of 19". For side-by-side rack mounting, the side-by-side mounting kit together
with the 19" rack panel mounting kit must be used. The mounting kit has to be ordered
separately.
Installation manual
Mounting bar
Screw
Side plate
80 mm
How to reach the connectors on the rear side of the IED.
Description
Screw
Screw
Rear protection cover
When mounting the plates and the angles on the IED, use screws that follow
the recommended dimensions. Using screws with other dimensions may
damage the PCBs inside the IED.
2
6
2
3
1
IEC06000135-2-en.vsd
Type
M4x10
M5x8
(Ordered separately)
Section 5
Mounting
-
M5x8
-
M11941-2 v5
2
IP10323-1 v1
M11974-3 v2
25