5.6
Positioning probe - electrode
Before fixing the burner to the boiler, check from
the opening of the blast tube that the probe and
the electrode are correctly positioned, as in
Fig. 16.
WARNING
If, in the previous check, the position of the probe or electrode
was not correct, is necessary:
remove the screw 1)(Fig. 15)
extract the inner part 2)(Fig. 15) of the head, and adjust
them.
Do not rotate the probe: leave it as in Fig. 16.
If it is located too close to the ignition electrode,
the control box amplifier may be damaged.
WARNING
Observe the dimensions shown in Fig. 16.
WARNING
Installation
Probe
Electrode
D3844
D8008
23
GB
1
2
Fig. 15
Fig. 16
20068131