Access To Head Internal Part; Positioning The Probe - Electrode - Riello RS 45 BLU Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

4.6

Access to head internal part

In order to reach inside the combustion head (Fig. 13) proceed as
follows:
 remove the screw 1) and the internal part 2).
 Fix the flange 9)(Fig. 12) to the plate of the boiler interposing
the insulating flange gasket 6)(Fig. 12) supplied with the
unit.
 Use the 4 screws, also supplied with the unit, after first
protecting the thread with an anti-locking product.
The seal between burner and boiler must be airtight.
4.7

Positioning the probe - electrode

Before securing the burner to the boiler, check
(through the opening of the blast tube) that the
probe and electrode are correctly positioned, as in
Fig. 14.
ATTENTION
If in the previous check the position of the probe or electrode was
not correct, remove the screw 1)(Fig. 13) extract the inner part
2)(Fig. 13) of the head, and adjust them.
D10833
PROBE
ELECTRODE
Installation
Do not rotate the probe but leave it as in Fig. 14; if
it is too close to the ignition electrode, it could
damage the control box amplifier.
ATTENTION
Respect the dimensions shown in Fig. 14.
ATTENTION
17
GB
D501
Fig. 13
Fig. 14
20191684

Advertisement

Table of Contents
loading

This manual is also suitable for:

20191662

Table of Contents