Selecting The Replacement Method - Omron C200HX Series Replacement Manual

From c200hx/hg/he to cj2
Table of Contents

Advertisement

2.

Selecting the replacement method

When C200H-series Basic I/O Units are replaced with CJ-series Basic I/O Units, rewiring is required. When
C200H-ID215 and C200H-OD215 C200H High-density I/O Units are replaced with CJ-series I/O Units, the same
connecting cables that were connected to C200H High-density I/O Units can be used.
Replacement method
Using Conversion Cables
for C200H High-density
I/O Units
Description
Replace C200H-ID215 with CJ1W-ID231, and
connect CJ1W-ID231 using the same
connecting cables used for C200H-ID215. In
the same way, replace C200H-OD215 with
CJ1W-OD231, and connect CJ1W-OD231
using the same cable used for C200H-OD215.
Pros: Rewiring of I/O Units is not required,
which reduces replacement time.
CJ-series Units
CPU
CJ1W-OD231
Conversion
Cable
XW2Z-S011
Connecting cable that was
connected to C200H-OD215
(reuse)
CJ1W-ID231
Conversion Cable
XW2Z-S010
Connecting cable that was
connected to C200H-ID215
(reuse)