Appendix C - Recommended connection - AK-PC 781
Function
The controller has a setting where you can choose between various
types of installation. If you use these settings, the controller will sug-
gest a series of connection points for the different functions. These
points are shown below. (The options shown are determined by
previous settings in the menu, e.g. cooling agent and "Pack type".)
Even if your installation is not 100% as described below, you can still
use the function. After use, you need only adjust the divergent set-
tings.
The given connection points in the controller can be changed if you
wish.
Appl.
Compressor
1
1a
2
2a
2b
2ab
3
3a
138
Fan
Description
LT
1 vsd comp.
1 single
LT
1 vsd comp.
1 single
CO2, Oil valve
MT
1 vsd comp.
2 single
vsd-fans
Boost
Gas cooler
Receiver
MT
1 vsd comp.
2 single
vsd-fans
Boost
Gas cooler
Receiver
Oil sep.
Oil receiver
Oil valve
MT
1 vsd comp.
2 single
vsd-fans
Boost
Gas cooler
Receiver
TW
HR
MT
1 vsd comp.
2 single
vsd-fans
Boost
Gas cooler
Receiver
Oil sep.
Oil receiver
Oil valve
TW
HR
MT
1 vsd comp.
3 single
vsd-fans
Boost
Gas cooler
Receiver
MT
1 vsd comp.
3 single
vsd-fans
Boost
Gas cooler
Receiver
Oil sep.
Oil receiver
Oil valve
Capacity controller RS8GG602 © Danfoss 2015-03
Module
Point number
1
2
Modul 1 -
LT Comp.
Loadshed
Controller
Release
1
Modul 2 -
Comp. 1
Comp. 2
AK-XM 102B
safety
safety
Modul 1 -
LT Comp.
Loadshed
Controller
Release
1
Modul 2 -
Comp. 1
Comp. 1
AK-XM 102B
safety
safety
Modul 1 -
MT Comp.
Loadshed
Controller
Request
1
Modul 2 -
Comp. 1
Comp. 2
AK-XM 102B
safety
safety
Modul 3 -
Volt
AK-XM 103A
input 1
Modul 4 -
AK-XM 208C
Modul 5 -
AK-XM 205A
Modul 1 -
MT Comp.
Loadshed
Controller
Request
1
Modul 2 -
Comp. 1
Comp. 2
AK-XM 102B
safety
safety
Modul 3 -
Reset Kom
Oil Low
AK-XM 103A
lockout
Receiver
Modul 4 -
AK-XM 208C
Modul 5 -
Oil lvl.
Oil lvl.
AK-XM 205A
comp. 1
comp. 2
Modul 6 -
AK-XM 205A
Modul 1 -
MT Comp.
Loadshed
Controller
Request
1
Modul 2 -
Comp. 1
Comp. 2
AK-XM 102B
safety
safety
Modul 3 -
Volt
AK-XM 103A
input 1
Modul 4 -
TW
TW
AK-XM 208C
Stw2
Stw3
Modul 5 -
TW
Flow Sw.
AK-XM 205A
enable
TW
Modul 1 -
MT Comp.
Loadshed
Controller
Request
1
Modul 2 -
Comp. 1
Comp. 2
AK-XM 102B
safety
safety
Modul 3 -
Reset Kom
Oil Low
AK-XM 103A
lockout
Receiver
Modul 4 -
TW
TW
AK-XM 208C
Stw2
Stw3
Modul 5 -
Oil lvl.
Oil lvl.
AK-XM 205A
comp. 1
comp. 2
Modul 6 -
TW
Flow Sw.
AK-XM 205A
enable
TW
Modul 1 -
MT Comp.
Loadshed
Controller
Request
1
Modul 2 -
Comp. 1
Comp. 2
AK-XM 102B
safety
safety
Modul 3 -
Volt
AK-XM 103A
input 1
Modul 4 -
AK-XM 208C
Modul 5 -
AK-XM 205A
Modul 1 -
MT Comp.
Loadshed
Controller
Request
1
Modul 2 -
Comp. 1
Comp. 2
AK-XM 102B
safety
safety
Modul 3 -
Reset Kom
Oil Low
AK-XM 103A
lockout
Receiver
Modul 4 -
AK-XM 208C
Modul 5 -
Oil lvl.
Oil lvl.
AK-XM 205A
comp. 1
comp. 2
Modul 6 -
AK-XM 205A
3
4
5
Loadshed
Main Sw.
2
VSD C.1
safety
Loadshed
Oil lvl.
Oil lvl.
Main Sw.
2
Comp. 1
Comp. 2
VSD C.1
safety
Loadshed
Sgc
Shp
Main Sw.
2
Comp. 3
VSD C.1
Fan 1
safety
safety
safety
Power loss Vhp
ICMTS
Saux 1
Loadshed
Sgc
Shp
Main Sw.
2
Comp. 3
VSD C.1
Fan 1
safety
safety
safety
Oil Hi
Power loss Vhp
Receiver
ICMTS
Oil lvl.
Oil Low
Oil Hi
comp. 3
Separ. 1
Separ. 1
Saux 1
Loadshed
Sgc
Shp
Main Sw.
2
Comp. 3
VSD C.1
Fan 1
safety
safety
safety
Power loss Vhp
ICMTS
TW
TW
HR
HR
Stw4
Stw8
Shr2
Shr3
HR
Flow Sw.
Saux 1
enable
HR
Loadshed
Sgc
Shp
Main Sw.
2
Comp. 3
VSD C.1
Fan 1
safety
safety
safety
Oil Hi
Power loss Vhp
Receiver
ICMTS
TW
TW
HR
HR
Stw4
Stw8
Shr2
Shr3
Oil lvl.
Oil Low
Oil Hi
comp. 3
Separ. 1
Separ. 1
HR
Flow Sw.
Saux 1
enable
HR
Loadshed
Sgc
Shp
Main Sw.
2
Comp. 3
Comp. 4
VSD C.1
Fan 1
safety
safety
safety
safety
Power loss Vhp
ICMTS
Saux 1
Loadshed
Sgc
Shp
Main Sw.
2
Comp. 3
Comp. 4
VSD C.1
Fan 1
safety
safety
safety
safety
Oil Hi
Power loss Vhp
Receiver
ICMTS
Oil lvl.
Oil lvl.
Oil Low
Oil Hi
comp. 3
comp. 4
Separ. 1
Separ. 1
Saux 1
AK-PC 781
6