Electrical Grounding Instructions: This appliance is
equipped with a three-prong (grounding) plug for your
protection against shock hazard and should be plugged
directly into a properly grounded three-prong receptacle.
Connect the Gas Supply Line
Check the Rating Plate attached by a steel cable to the
firebox, to confirm that you have the appropriate firebox
for the type of fuel to be used. The Stardance may be
converted from one gas to another using the appropriate
Fuel Conversion Kit.
In the U.S.; Gas connection should be made in accordance
with current National Fuel Gas Code, ANSI Z223.1/NFPA 54.
Since some municipalities have additional local codes, be
sure to consult your local authority.
In Canada; consult the local authority and CSA-B149.1
installation code.
NOTE: Always check for gas leaks with a mild soap and
water solution. Do not use an open flame for leak testing.
Light the pilot according to the directions in the Operation
section of this manual.
Burner Information
The appliance must only use the gas specified on the rating
plate, unless converted using a Vermont Castings Fuel
Conversion Kit.
2525
WARNING
Vermont Castings • Stardance SDDVT Installation Manual_R23 • 11/21
!
This appliance should only be connected by a qualified gas
technician. Test to confirm manifold pressures as specified
below.
The Stardance Heater and its individual shutoff valve must
be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess
of 1/2 psig (3.5 kPa).
The Stardance Heater must be isolated from the gas supply
piping system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping system
at test pressure equal to or less than 1/2 psig.
There must be a gas shutoff between the stove and the
supply.
In order to connect Natural Gas, use a fitting with 1/2" NPT
on the valve side and 1/2" natural gas supply line with an
input of 38,000 BTUs at a manifold pressure of 3.5" between
minimum inlet supply of 5.5" w.c. and maximum of 10.0" w.c.
In order to connect Propane, use a fitting with 1/2" NPT
on the valve side and 1/2" propane gas supply line with
an input of 36,000 BTUs at a manifold pressure of 10.0"
between a minimum inlet supply of 11.0" w.c. and maximum
of 13.0" w.c.
THIS APPLIANCE SHOULD BE CONNECTED TO THE
GAS SUPPLY ONLY BY A QUALIFIED GAS SERVICE
TECHNICIAN. FOLLOW ALL LOCAL CODES.
THERE MUST BE A GAS SHUT-OFF BETWEEN THE
STOVE AND THE SUPPLY.
CAUTION
3-90-30007467