 For 4 pipes:
(7) Check the smoothness of drain after installation.
(8) Check the drain state by imitating 600cc water slowly from the outlet vent or test hole.
(9) Check the drain in the state of refrigerating after installation of the electric circuit.
Warning: Before obtaining access to terminals, all supply circuits must be disconnected.

4. ELECTRIC WIRING

(1) All field supplied parts and materials must conform to local laws and regulations.
(2) For electric wiring, refer to WIRING DIAGRAM attached to the unit body.
(3) All wiring must be performed by a skilled technician.
(4) A circuit breaker capable of shutting down power supply to the entire system and which have at
least mm contact separation in each jole must be installed in the fixed wiring.
(5) Earth properly.
(6) Wiring must conform to national laws and regulations.
(7) The fixed wiring must be installed with a protector with no more that 30 mA leakage current.
(8) If the supply cord is damaged, it must be replaced by the manufactory or its service agents or a
similarity qualified person in order to avoid a hazard.
UNIT INSTALLATION