Gree FP-8XD-E Service Manual page 22

Commercial air conditioners cassette type fan coil unit
Hide thumbs Also See for FP-8XD-E:
Table of Contents

Advertisement

Package
Body
dimension
Panel TB03
(W×D×H)
Body
Net weight
Panel TB03
Body
Gross
weight
Panel TB03
20'GP (with panel TB03)
Loading
40'GP (with panel TB03)
quantity
40'HQ (with panel TB03)
Testing condition:
For 60Hz :
The FCU designed for installation indoor. The environmental temperature is from 5° C to 43° C, water
working temperature is from 7° C to 60° C.
The temperature exchange efficiency and enthalpy exchange efficiency are tested under these testing
conditions as below:
(a) Cooling capacity: air 27° C DB, 19.5° C WB, water temperature: intake 7° C, outlet12° C.
(b) Heating capacity: air 21° C DB, Water temperature intake 60° C, the water-flow volume is same as
Cooling capacity .
(c) Freeze-up : air 27° C DB, 24° C WB, water temperature intake 6° C, outlet 9° C.
(d) Sound power level according to ISO 5151. Sound pressure level are calculated at the below of
air-outlet 1m and 1m distance. The noise are tested before leaving factory.
For 50 Hz :
The FCU designed for installation indoor. The environmental temperature is from 5° C to 43° C, water
working temperature is from 7° C to 60° C.
The temperature exchange efficiency and enthalpy exchange efficiency are tested under these testing
conditions as below:
(a) Cooling capacity: air 27° C DB , 19° C WB, water temperature intake 7° C, outlet 12° C.
(b) Heating capacity: air 20° C DB , Water temperature intake 50° C, outlet 40° C.
(c) Freeze-up : air 27° C DB, 24° C WB , water temperature 6° C intake , 10° C outlet .
(d) Sound power level according to ISO 5151. Sound pressure level are calculated at the below of
air-outlet 1m and 1m distance. The noise are tested before leaving factory.
For 4 pipes:
The FCU designed for installation indoor. The environmental temperature is from 5° C to 43° C, water
working temperature is from 7° C to 70° C.
The temperature exchange efficiency and enthalpy exchange efficiency are tested under these testing
conditions as below:
PRODUCT
mm
960×960×257
mm
1033×1038×133
kg
25.0
kg
7
kg
33.0
kg
11
56
131
147
20
960×960×257
960×960×310
1033×1038×133
1033×1038×133
25.0
27.0
7
33.0
34.0
11
11
56
50
131
121
147
134
960×960×394
1033×1038×133
32.0
7
7
41.0
11
42
98
112