TABLE 2
LC1000/TEC-EYE Passwords (Defaults)
User
Technician
Engineer
Use UP or DOWN keys and ENTER key to enter password
Menu Screens and Password Levels
A
System Config: User (2000)
B
Adv Sys Config: Technician (1313)
C
I-O Config: Technician (1313)
D
On/Off: User (2000)
E
Alarm Logs: User (2000)
F
Settings
Date/Time: Technician (1313)
Language: User (2000)
Network Config: Technician (1313)
Serial Ports: Technician (1313)
Initialization
Clear Logs: User (2000)
System Default: Engineer (9254)
Restart: User (2000)
Parameter Config: Engineer (9254)
Alarm Export: User (2000)
G
Logout: Used to log out of the current password
level. Entering back into the menu requires
password.
Addressing Wall-Mount Units
Each unit must have a unique address for the system
to operate correctly with the LC controller (Ex: 1, 2, 3,
...14 depending on the number of units). The wall-
mount unit address is displayed in the upper right
corner on the Status screen on the TEC-EYE display
(see Figure 2 on page 6).
To change the unit address:
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config;
press ENTER key.
4. Press ENTER key to scroll to Unit Address (see
Figure 10).
5. Press UP or DOWN keys to change the address to a
value between 1 and 14.
NOTE: Each unit must have a unique address for the
2000
1313
9254
Setting Unit Zone
To assign zones:
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
3. Press UP or DOWN keys to scroll to Sys Config;
4. Press ENTER key to scroll to Unit Zone (see Figure
5. Press UP or DOWN keys to change value to desired
Additional Features
Model/Serial Number Retain Feature
Model numbers and serial numbers will be retained
through most software updates. It still remains good
practice to verify the software version, model numbers
and serial numbers of any wall-mount unit after a
software update, as some functionality of the MULTI-
TEC wall-mount unit require a specific model number.
Time/Date/Timezone Sync
On MULTI-TEC wall-mount unit models with a software
version number MTS1000.2.0.0 and higher, when the
wall-mount unit is connected and correctly addressed
to a LC6000 supervisory controller, local time, date,
and timezone information will be synced from the
LC6000. This feature allows for faster set-up and
correct correlation between alarm logs.
Executing a Run Test
Execute a run test on each unit to verify the equipment
is functioning correctly.
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
communication to work properly. Bard also
recommends physically labeling each unit for
ease in identification.
FIGURE 10
Unit Configuration
USER password 2000.
press ENTER key.
10).
zone.
USER password 2000.
Manual 2100-665G