Clear Unit Alarm Logs On Each Unit; Setting Up Lc6000 For Operation; Set Lc Controller Date And Time - Bard MULTI-TEC W18AAPA Service Instructions Manual

Wall-mount air conditioner part of the bard free cooling system
Table of Contents

Advertisement

5) Press ENTER key to scroll to Run Test Enable
parameter (see Figure 30).
6) Press UP or DOWN key to change value to ON.
The run test will begin.
FIGURE 30
Executing Run Test
Step Action
A
Open economizer damper
B
Close economizer Damper
C
Turn on compressor
D
Enable second stage
E
Open reheat valve
F
Turn all cooling off
G
Turn on electric heat
H
Turn on electric heat stage 2
I
Turn off all heating
Parameter Description
Damper Time: This is the time (in seconds) allowed for
both the opening sequence and closing sequence.
Heat/Cool Time: This is the time (in seconds) allowed
for cooling sequence and heating sequence.
Status: This will display what the unit is doing as
the run test progresses. The following messages may
appear:
1. Not Active
2. Opening Damper
3. Closing Damper
4. Compressor Stage 1
5. Compressor Stage 2
6. Reheat Valve Open
7. Cooling Off
8. Electric Heat Stage 1
9. Electric Heat Stage 2
10. Heating Off
11. Run Test Stop
The unit will determine which items to test based on
the unit model number.
Manual 2100-676D
Page
38 of 45

3. Clear Unit Alarm Logs on Each Unit

Time Required
Damper Time (150s)
Damper Time (150s)
Heat/Cool Time (60s)
Heat/Cool Time (60s)
Heat/Cool Time (60s)
--
Heat/Cool Time (60s)
Heat/Cool Time (60s)
--
After each of the wall-mount units have been

Setting Up LC6000 for Operation

The LC6000 controller will be used for the remaining
LC6000 Status Screen
The Status screen is the default start-up screen and
also the return screen after 5 minutes of no activity on
the LC6000. The screen can be accessed any time by
pressing the ESCAPE key repeatedly.
The Status screen on the LC6000 displays the current
date, time, unit displayed, zones and system status
(see Figure 34).

4. Set LC Controller Date and Time

Units may have alarms logged due to testing. Unit
alarm logs must be cleared at time of installation.
To clear the wall-mount unit alarm logs:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter TECHNICIAN password 1313.
3) Press UP or DOWN keys to scroll to Settings;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Initialization; press ENTER key.
5) Press UP or DOWN keys to scroll to
Initialization 1/5; press ENTER key.
6) Press ENTER key to scroll to Delete alarm
logs? (see Figure 31).
7) Press UP or DOWN key to change NO to YES.
8) Press ENTER key to clear all alarm logs.
FIGURE 31
Clearing Unit Alarm Logs
addressed, had a run test performed and had the alarm
logs cleared, the rest of the system set up can proceed.
steps in the set up process.
1) Press MENU key to access the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter USER password 2000.