Using The Tec-Eye Tm; Tec-Eye Hand-Held Diagnostic Tool; Figure 2 Tec-Eye Display And Interface; Figure 3 Tec-Eye Connection To Unit Control - Bard MULTI-TEC W18AAPA Service Instructions Manual

Wall-mount air conditioner part of the bard free cooling system
Table of Contents

Advertisement

USING THE TEC-EYE
TEC-EYE (Bard P/N 8301-059) Display and Interface (Status Screen Shown)
ALARM KEY
MENU KEY
ESCAPE KEY
ALARM KEY
Allows viewing of active alarms
Silences audible alarms
Resets active alarms
MENU KEY
Allows entry to Main Menu
ESCAPE KEY
Returns to previous menu level
Cancels a changed entry

TEC-EYE Hand-Held Diagnostic Tool

The microprocessor control used in the MULTI-TEC
wall-mount air conditioners allows for complete control
and monitoring through the use of the provided TEC-
EYE hand-held monitor. This comprehensive service
tool utilizes the latest in state-of-the-art technology
including a large, easy-to-read backlit LCD graphic
display.
The menu driven interface provides users the ability
to scroll through two menu levels: Quick Menu and
Main Menu. The menus permit the user to easily view,
control and configure the unit.
The controller is completely programmed at the factory;
the default setpoints and their ranges are easily viewed
and adjusted from the TEC-EYE display. The program
and operating parameters are permanently stored
on FLASH-MEMORY in case of power failure. The
controller is designed to manage temperature levels to
a user-defined setpoint via control output signals to the
wall mount air conditioning system.
The TEC-EYE connects to the wall-mount unit control
board via an RJ11 modular phone connector as shown
in Figure 3.
Manual 2100-665G
Page
6 of 28
TM
FIGURE 2
UP KEY
Steps to next screen in the display menu
Changes (increases) the value of a modifiable field
ENTER KEY
Accepts current value of a modifiable field
Advances cursor
DOWN KEY
Steps back to previous screen in the display menu
Changes (decreases) the value of a modifiable field
When not being used, the TEC-EYE hand-held
diagnostic tool should be stored inside or near the
LC6000 controller. Do not let the TEC-EYE leave the
shelter.
FIGURE 3
TEC-EYE Connection to Unit Control
Modular Phone Connector for
TEC-EYE Hand-Held Diagnostic Tool
UP KEY
ENTER KEY
DOWN KEY