Program Version; Software Versioning Guide; Alarm Log; Menu Screens And Password Levels - Bard MEGA-TEC W090A Service Instructions Manual

Wall-mount air conditioner
Table of Contents

Advertisement

Program Version

The Software Version screen displays the model
number of the unit as well as all program version
information for the PLC (see Figure 7). This information
can be used to determine whether a software update
may be required based on information found in the
software change log. This change log can be found at
http://www.bardhvac.com/software-download/.
FIGURE 7
Software Version

Software Versioning Guide

SoftwareName.x.y.z
Software Name: The name of the software is the
base part number used to identify which product the
software is used in.
TABLE 2
Software Versioning Guide
Product
MULTI-TEC
FUSION-TEC (WR)
MEGA-TEC
LC6000
X: The letter X represents a major change to the
software effecting product compatibility or function of
the equipment.
Y: The letter Y represents a minor change to the
software that either adds, removes, or alters a feature
of the equipment.
Z: The letter Z represents a change to the software that
fixes existing features or user interface.

Alarm Log

The alarm log screens show a log of each alarm. There
will be a log for when alarm occurred and if the alarm
auto clears, it will show when the alarm cleared. See
page 12 for information on clearing alarms.
Manual 2100-671C
Page
10 of 59
Software Name
MTS1000
WTS1000
MGS1000
LCS6000
NOTICE
It is important to check the software version
during installation to ensure that the latest
version has been installed. Current software
versions, change log and installation
instructions are available on the Bard website at
http://www.bardhvac.com/software-download/

Menu Screens and Password Levels

A
System Config: A1-A5 User (2000)
B
Adv Sys Config: B1-B4 Technician (1313)
C
I/O Config: Technician (1313)
D
On/Off: User (2000)
E
Alarm Logs: User (1313)
F
Settings
Date/Time: Technician (1313)
Password Change
Initialization
Alarm Initialization: User (2000)
Default Installation: Engineer (9254)
Parameters Import/Export: Engineer (9254)
Alarm Export: User (2000)
G
Logout: Used to log out of the current password level.
Entering back into the menu requires password.
TABLE 3
LC6000/TEC-EYE Passwords (Defaults)
User
Technician
Engineer
Use UP or DOWN keys and ENTER key to enter password.
The passwords listed above are the default passwords.
End users can change these passwords if additional
security is desired.

Executing a Self Test

This unit has the ability to perform a self test that will
operate all available unit functions in order to quickly
determine unit operation. Self test parameters are not
adjustable.
The self test will automatically skip sections of the test
based on the model number entered into the controller.
If position 10 of the model number is B (to indicate
a blank off economizer option), steps A and B will be
skipped. If positions 8 and 9 of the model number
indicate a 0Z (0 kW) option, steps G,H and I will be
skipped. If position 8 and 9 indicate a 09 (9 kW)
option, step H will be skipped.
2000
1313
9254