Quick Menu
Setpoints
If at any time the unit(s) loses communication with the
LC6000 controller, the unit(s) will go to stand alone
mode. The setpoints are synced with the LC6000 when
communication is established. The unit will save and
control to these values until communication is re-
established.
To change the cooling and heating setpoints:
1. From the Status screen, press UP or DOWN key
until Quick Menu displays Setpoints icon. Press
ENTER key.
2. Press ENTER key to scroll to the selected choice
(see Figure 5).
3. Press UP or DOWN key on desired value until value
displays correctly.
4. Press ENTER key to submit value and move to next
parameter.
5. Press ESCAPE key until Main Menu screen is
displayed.
FIGURE 5
Cooling and Heating Setpoints
Information
These screens show unit run hours, averages and
software version information (see Figures 6, 7 and 8).
FIGURE 6
Last 24 Hour Tracking
Manual 2100-665G
Page
8 of 28
FIGURE 7
Last 24 Hour Tracking
FIGURE 8
Software Version Information
Data (Alarm) Log
The alarm log screens show a log of each alarm (see
Figure 9. There will be a log for when alarm occurred
and if the alarm auto clears, it will show when the
alarm cleared. See page 12 for instructions on clearing
the alarm logs.
FIGURE 9
Alarm Log Screen Breakdown
NOTE
Screenshots shown in this manual reflect
default settings (when applicable).
Alarm Log Number
Alarm Date/Time
Alarm Index
Number
Alarm Description
Alarm Event Type
(Start/Stop)