2.7

Equipment Operates but does not Provide Heating

All models of SkyAir series
Applicable Model
 Overcharge of refrigerant
Supposed
 Air mixed in refrigerant system
Causes
 Defective pressure switch
 Defective magnetic switch for outdoor unit fan motor
 Defective aux. relay for outdoor unit fan motor
 Soiled heat exchanger of outdoor unit
 There is an interfering item in airflow of outdoor unit.
 Defective outdoor unit fan
 Soiled air filter of indoor unit
 Soiled heat exchanger of indoor unit
 There is an interfering item in airflow of indoor unit.
 Defective indoor unit fan
Service Diagnosis