Malfunction Of Motion Sensor / Floor Temperature Sensor - Daikin GQI-Eco Series Service Manual

R-410a 50hz
Table of Contents

Advertisement

ESIE15-13B
4.11 Malfunction of Motion Sensor / Floor Temperature
Sensor
CE
Remote
Controller
Display
Indoor unit: FXYFP~B
Applicable
Models
Detect by a signal outputted from the sensor.
Method of Error
Detection
When malfunction is detected by a signal outputted from the sensor.
Error Decision
Conditions
 Disconnection of connector from or failure of motion sensor [CE-01]
Supposed
 Failure of floor temperature sensor (wiring disconnection in temperature compensation
Causes
 Failure of floor temperature sensor (wiring disconnection in temperature compensation
 Failure of floor temperature sensor element [CE-04]
Troubleshooting
Service Diagnosis
circuit) [CE-02]
circuit) [CE-03]
The contents of individual failures
vary with detailed malfunction code.
Ensure the detailed malfunction code,
and then go to the relevant Diagnosis
Flowchart.
Detailed malfunction code
CE-01
Detailed malfunction code
CE-02
Detailed malfunction code
CE-03
Detailed malfunction code
CE-04
Troubleshooting by Remote Controller
Go to Diagnosis Flowchart-1.
Go to Diagnosis Flowchart-2.
Go to Diagnosis Flowchart-3.
Go to Diagnosis Flowchart-4.
133