Removal Of Solenoid Valve And Shunt - Daikin FTKE25BVM Service Manual

Super multi nx c-series
Hide thumbs Also See for FTKE25BVM:
Table of Contents

Advertisement

Si12-411A
2.8
Removal of
Procedure
Step
Before taking this
procedure, make sure
there is no refrigerant gas
left in the refrigerant
pipes.
Disconnect the 2
1
brazed points (a) and
(b) in this order.
Remove the putty of the
2
shunt.
Disconnect the 5
3
brazed points of the
shunt.
Removal Procedure
Solenoid Valve
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)
and
Shunt
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the gas
welding rod.
If refrigerant gas leaks during
the job, ventilate the room.
(Bear in mind that if the
refrigerant gas is exposed to
open flames, noxious gas may
be generated.)
Reassembling precautions
Wrap the solenoid valve body
with wet cloth. Splash water
over the cloth before it is dried
to prevent the valve from being
overheated.
Points
Caution
Warning
255

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents