Removal Of Shunt - Daikin FTKE25BVM Service Manual

Super multi nx c-series
Hide thumbs Also See for FTKE25BVM:
Table of Contents

Advertisement

Si12-411A
1.8
Removal of
Procedure
Step
Remove 6 screws of
1
the tie wire presser
plate.
Remove 4 screws of
2
the right side panel.
3
Remove the putty.
Before taking this
procedure, make sure
there is no refrigerant gas
left in the refrigerant
pipes.
Disconnect the 5
4
brazed points of the
shunt.
Removal Procedure
Shunt
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Outdoor Unit (80 / 90 Class)
Points
Fasten the rubber packing
with double-faced adhesive
tape when mounting.
Caution
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the gas
welding rod.
Warning
If refrigerant gas leaks during
the job, ventilate the room.
(Bear in mind that if the
refrigerant gas is exposed to
open flames, noxious gas may
be generated.)