Wine Guardian TTW009 Installation, Operation And Maintenance Manual page 40

60hz;50hz
Table of Contents

Advertisement

RH% Sensor
Calibration
Differential
temperature
adjustment
Deadband setting
Test mode setting
System Selection
40
Setting 16
This setting will allow the adjustment of RH%
reading by +/-10%. Factory default is 13%RH.
Setting 17
Press "Settings" button to advance to Setting
17
Press the "Up" or "Down" buttons to adjust to
the desired setpoint.
This setting changes the system/compressor; turn
on temperature above setpoint. Factory default is
set to 1 Deg F.
Example: Sensor reading = 55 Deg F (12 Deg C)
Setting 17 Set to +3 Deg F
System/compressor turns on at 58 Deg F. (14 Deg
C)
Setting 18
Press "Settings" button to advance to Setting
17.
Press the "Up" or "Down" buttons to adjust to
the desired setpoint.
This setting is the minimal allowable temperature
difference between heating and cooling setpoints.
Maximum is 5 Deg F,(-15 Deg C) minimum is 1
Deg F. Factory default is set to 2 Deg F (-16 Deg
C)
Setting 19
Press "Settings" button to advance to Setting 7.
Press the "Up" or "Down" buttons to adjust to
the desired setpoint. When set to one the
controller will automatically turn on all outputs
with the exception of electric heat. Factory
default is zero.
Zero (0) = Off.
One (1) = On
Setting 20
DO NOT CHANGE