Maintenance; Condensate Drain - Fedders A7D18E2B User Manual

Room air conditioners for double hung windows & through-the-wall installation
Table of Contents

Advertisement

Available languages

Available languages

THRU-WALL INSTALLATION
INSTALLATION

Condensate Drain

A condensate drain is provided to divert excess water when air
conditioner is installed over a doorway or sidewalk.
OPERATION
1. Pry cap plug from the condensate drain (located on underside of
ELECTRONIC CONTROLS
bottom pan). Use a 5/8" pipe tap and fully thread the condensate
drain (Fig. 20).
2. Screw a 5/8" pipe fitting into the condensate drain. The fitting

MAINTENANCE

should be protruding approximately 1/2" above the bottom pan
AIRFLOW / FILTER
when fully threaded into the condensate drain (Fig. 21).
3. If an open drain source is used to dispose of condensate, plastic or
rubber tubing may be run directly from the pipe fitting to the open
drain source. If closed drain source (internal structural plumbing) is
used, a "P" trap must be between the 5/8" pipe fitting and the
closed drain source (Fig. 22).
Consult your authorized dealer or importer for alternative
installation instructions.
Caution: Do not drill a hole in bottom pan. Unit is designed to
operate with approximately 1/2" of water in bottom pan.
Do not remove the cap plug, unless the condensate drain is
used.
20
21
B
22
22
E
Cap plug
A
Bottom pan
B
Condensate drain
C
5/8" pipe fitting fully threaded
D
into condensate drain
"P" trap
E
To closed drain source
F
6
A
C
D
F

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

A7d18e7c

Table of Contents