Page 2
会也可能不会含有所有所列的部件。This table shows where these substances may be found in the supply chain of Prodigit electronic information products, as of the date of sale of the enclosed product. Note that some of the component types listed above may or may not be a part of the enclosed product. ○:表示该有毒有害物质在该部...
Page 3
Failure to comply with these precautions or with specific warnings elsewhere in this manual violates safety standards of design, manufacture, and intended use of the instrument. PRODIGIT assumes no liability for the customer's failure to comply with these requirements.
Page 4
DECLARATION OF CONFORMITY Company Name: PRODIGIT ELECTRONICS CO., LTD Address: 8F, No.88, Baojhong Rd., Sindian District, New Taipei City, Taiwan. Declares under sole responsibility that the product as originally delivered Product Names: DC Electronic Loads Model Numbers: 3110, 3111, 3114, 3117, 3119...
Page 5
SAFETY SYMBOLS Direct current (DC) Alternating current (AC) Both direct alternating Three-phase alternating current Protective earth (ground) On (Supply) Off (Supply) Fuse Caution!Refer to this manual before using the meter. Caution, risk of electric shock CAT IV – Is for measurements performed at the source of the low-voltage installation.
3.125A is possible. Conversely if the 3110 is required to sink 50A the voltage must be limited to 5V. The power contour of each load module in the 3110 series is shown in Fig 1-1, to 1-5.
2 PRODIGIT Voltage 250W Power Curve 3.125A Current Fig 1-1 3110 80V/50A/250W power contour Voltage 350W Power Curve 1.2V 4.375A Current Fig 1-2 3111 80V/70A/350W power contour Voltage 500V 350W Power Curve 23.3V 0.7A Current Fig 1-3 3114 500V/15A/350W power contour...
Constant Current (CC) mode, Constant Resistance (CR) mode, Constant Voltage (CV) mode, and Constant Power (CP) mode. 1.1.1. CC Mode With the operating mode of Constant Current, the 3110 series electronic load will sink a current in accordance with the programmed value regardless of the input voltage (see Fig.1-6).
Fig 1-8 Constant Voltage mode 1.1.4. CP Mode: At Constant Power mode, the 3110 series Electronic Load will attempt to sink load power (load voltage * load current) in accordance with the programmed power. (See Fig 1-9). Fig 1-9 Constant Power mode...
3110 Series Operation Manual 5 1.1.5. Dynamic Waveform Definition Along with static operation the 3110 load modules are built with a Dynamic mode for operation in Constant Current (CC), Constant Resistance (CR) or Constant Power (CP). This allows the test engineer to simulate real world pulsing loads or implement a load profile that varies with time.
6 PRODIGIT In cases where the transition from one setting to another is small, the small signal bandwidth (of the load) limits the minimum transition time for all programmable slew rates. Because of this limitation, the actual transition time is longer than the expected time based...
3110 Series Operation Manual 7 Features The main features of the 3110 series of load modules are highlighted below. • 5 digital V / A / W Meter. • High-speed measurement and communication transmission. • V.A.W. values can be displayed simultaneously.
Prodigit's sales and service office or representative. Your 3110 series was shipped with a power cord for the type of outlet used at your location. If the appropriated cord was not included, please contact your nearest sales office to obtain the correct cord.
BEFORE replacing the fuse you must switch off the unit and mains power outlet and disconnect the plug of the AC Power cable from the input socket of the 3110 series. If prior to exchanging the fuse, there is any abnormal noise or odour do not use the unit.
12 PRODIGIT 2-3 Environmental requirements • Indoor use. • Measurement Category I. • Pollution Degree 2. • Relative Humidity 80% Max. • Ambient Temperature 0 to +40°C • Altitude up to 2000m. • The equipment is not for measurements performed for CAT II, III and IV.
2.6.1 Check that the POWER switch is in the off (O) position 2.6.2 Check the rear panel voltage selector of the 3110 series is Correctly set. 2.6.3 Check that nothing is connected to the DC INPUT (load input terminals) on the Front panel of the 3110 load .
Generates a large voltage at both ends of the wiring cable. This voltage applies to all of the Load input terminals of the 3110 series when the impedance of the EUT is relatively small. The voltage generated by the load wire inductance (L) and the current variation (I) is Expressed using the following equation.
3110 Series Operation Manual 15 In such event, the electronic load (3110 series) may generate unstable oscillation. In such condition, the input voltage may exceed the maximum input voltage and Cause Damage to the 3110 Series. Current △I △T Voltage at Load Input Terminal...
16 PRODIGIT To prevent problems, connect the 3110 series and the equipment under test using the Shortest Twisted Wire possible to keep the voltage caused by inductance between the Minimum operating Voltage and the maximum input voltage range or set a low slew rate.
3110 Series Operation Manual 17 Chapter 3 Operation This chapter describes the front panel operation of each 3110 series load. Please note that RS- 232C/USB remote programming terms are detailed in the separate 3110 series operation manual. 3-1. Dimension 3110, 3111, 3114 Dimension...
The following sketch shows the layout of the front panel of the unit. Please refer to the relevant Section as indicated by the number assigned to a front panel function. Fig 3-1 Front panel of 3110 Series LCD 3.2.1. Model number and sink ranges The model number along with maximum voltage, current and power values are Detailed in this position at the top of the load module’s front panel.
Page 28
20 PRODIGIT Remote 3.2.4. LCD Indicator If the REMOTE LCD Indicator is illuminated this means that the unit is operating remotely via one of the optional interfaces. While REMOTE is lit it is not possible to make settings manually at the front panel. The LOCAL button on the mainframe can be used to revert back to front panel control.
Page 30
22 PRODIGIT 3.2.7.3. DYN setting. Each press of the DYN setting button changes the text on The middle LCD. The sequence and the corresponding setting value Shown on the bottom display are as follows: T-Hi (time high) displays the set value in milliseconds “ms”...
Page 31
3110 Series Operation Manual 23 3.2.7.7. OCP test. This allows the parameters of the over current protection test To be set up. Each press of the OCP button moves the setting function. The sequence of the OCP test along with the setting value is as follows: OCP Press Start (pressing the red START/STOP button starts the test) ...
Page 32
3.2.11. Key and LED The 3110 series Load Module features 2 setting ranges for CC, CR, CV & CP Operation. This allows improved resolution for setting low values. When left in the Default AUTO mode the changeover between ranges is automatic depending on The setting value entered.
Page 33
3110 Series Operation Manual 25 LEVEL 3.2.12. key and LED The LEVEL button is used to program a High or Low load value. The setting value Changes between current, resistance, voltage or power depending whether CC, CR, CV or CP mode has been selected. If the LED is lit then the High level value Setting Has been enabled.
Page 34
26 PRODIGIT The High and Low levels of load resistance can be preset on the lower 5 Digit LCD. The "Ω" LED will be lit indicating the setting value is ohms. 3.213.3. Constant Voltage (CV) mode: The High and Low levels of load voltage can be preset on the lower 5 Digit LCD.
Page 35
3110 Series Operation Manual 27 Setting Upper limit voltage VH , Middle 5 digit LCD display「V-Hi」,lower 5 Digit LCD display the unit is "V”, the V-Hi set range from 0.000 V to 81.000V step 0.001V by rotating the Setting knob.
Page 36
28 PRODIGIT Setting Upper limit current IH , Middle 5 digit LCD display「I-Hi」,lower 5 Digit LCD display the unit is "A”, the I-Hi set range from 0.000 A to 50.400A Step 0.001A by rotating the Setting knob. Setting lower limit current IL , Middle 5 digit LCD display「I-Lo」,lower 5 ...
Page 37
3110 Series Operation Manual 29 CC mode, press limits key to set the V-Hi and V-Lo voltage upper and lower Limits of the GO / NG. Current Load Current Voltage High CC Dynamic Mode, press key to set the Level Hi and Level Low voltage ...
Page 38
30 PRODIGIT CV mode, press limits key to set the I-Hi and I-Lo Current upper and lower Limits of the GO / NG. High Load Current Voltage Load lnput Voltage CP mode, press limits key to set the W-Hi and W-Lo power upper and lower ...
Page 39
3110 Series Operation Manual 31 T_Hi (time the waveform is high) T_Lo (time the waveform is low) RISE (rise time) FALL (fall time ) The time that the waveform is high includes the rise time and is set in “ms”...
Page 40
32 PRODIGIT Press DYN setting key, LED will ON Setting level High Period, Middle 5 digit LCD display will show 「T-Hi」 Lower 5 digit LCD display will show setting value, the unit is “ms” , The T-Hi Set range from 0.050 ms to 9999 ms step 0.001ms by rotating the setting Knob.
Page 41
3110 Series Operation Manual 33 Config 3.2.16. The CONFIG key allows the sense function to engage automatically or switched ON. The CONFIG key also enables the LOAD to automatically turn ON/OFF When a voltage level is reached. The polarity symbol can also be switched via the CONFIG menu.
Page 42
34 PRODIGIT Note 1: The adjustable LDon (LOAD ON) voltage is valid for CC, CR & CP operating Modes. The adjusted LDon voltage will not operate in CV mode. Note 2: The LDon (LOAD ON) voltage setting cannot be lower than the LDoff (LOAD OFF) voltage.
Page 43
3110 Series Operation Manual 35 Set Load polarity, the middle of the 5 digit LCD display will show "POLAR", Lower the 5 digit LCD display "will show + LOAD" or "-LOAD", use the knobs And key settings "+ LOAD" or "-LOAD".
Page 44
36 PRODIGIT setting the short test time,The LCD display show 「SHORT」 on upper 5 digits LCD display,shows 「TIME」on middle 5 digits LCD display,lower 5 digit LCD display 「CONTI」, the unit is "ms". TIME: setting the short test time, The LCD display show 「SHORT」 on ...
Page 45
3110 Series Operation Manual 37 V-Lo : Short test voltage check lower limitation setting, The LCD display shows 「SHORT」on upper 5 digit LCD display, Middle 5 digit LCD display value 「V-Lo」,lower 5 digit LCD display setting , the unit is "V", the V-Hi setting range from 0.000V to 81.000V step 0.001V by rotating the setting...
Page 46
38 PRODIGIT The setting sequence is shown below: OCP PRESS START (pressing the red start/stop key starts test) OCP I STAR (current starting point of the OCP test) OCP I STEP (value of incremental current steps from I START) ...
Page 47
3110 Series Operation Manual 39 ISTOP: setting the stop current point, The LCD display shows 「OCP」on upper 5 digit LCD display, Middle 5 digit LCD display「ISTOP」,lower 5 digit LCD display setting value, the unit is "A", the setting range is 0.000A to the full scale of the CC mode specification.
Page 48
40 PRODIGIT 3.2.19. The OPP key allows the parameters of an Over Power Protection test to be entered. The OPP test will ramp up the load power in steps to validate the Device under Test’s (DUT) protection and behavior. A voltage threshold level can be set.
Page 49
3110 Series Operation Manual 41 PSTAR: setting the start power, The LCD display shows 「OPP」on upper 5 digit LCD display, Middle 5 digit LCD display「PSTAR」,lower 5 digit LCD value display setting , the unit is "W", the setting range is 0.00W to the full scale of the CP mode specification.
Page 50
42 PRODIGIT (a) The voltage level of the DUT falls below the set voltage threshold (OPP Vth) during the test (b) The current taken from the DUT reaches the OPP P STOP setting. Note 2: The message PASS will be displayed if the DUTs voltage stays above the set threshold.
Page 51
3110 Series Operation Manual 43 RIGHT ARROW key moves the setting selection one digit to the right. UP ARROW key increases the setting value. DOWN ARROW key reduces the setting value. Note 1: In CR MODE the UP ARROW key and CLOCKWISE operation of The ROTARY Knob reduces the resistance.
3.2.23. V-sense input terminal The V-sense terminals can be used to compensate for a voltage drop in the load lines between the power supply and the 3110 series Electronic Load. This is a useful feature useful when the load current is relatively high.
For example. 3110: Imax = 50A therefore I-monitor 10V = 50A so 1V = 5A Please refer to the specification Table 1-1 for the maximum current that each 3110 series module is capable of. The current monitor of this unit is NOT isolated. Please be careful when you connect an oscilloscope.
46 PRODIGIT Connecting the I-monitor to an oscilloscope When you connect this product to an oscilloscope, please ensure the correct polarities of the connecting probes as shown in Fig. 3-4. Fig 3-4 (Correct) Connections to an oscilloscope Fig 3-5 (Wrong) Connections to an oscilloscope If the probes connection is reversed as shown in Fig 3-5, a large current would flow through the probe and the internal circuitry of the oscilloscope is likely to be damaged.
Page 55
3110 Series Operation Manual 47 SURGE 3.2.25. Press the SURGE button to enter the SURGE setting mode. The LED indicator is ON and its setting sequence is as follows: SUR._I NOR._I S.TIME S.STEP ...
Page 56
48 PRODIGIT BATT 3.2.26. Press the BATT key to enter the BATT setting mode, the LED indicator is ON, and The setting sequence is as follows: DISCH MODE CC DISCH CC STOP VOLT.V STOP TIME.S STOP CAP.AH...
Page 57
3110 Series Operation Manual 49 Set DISCH CC, LCD displays “DISCH”, the middle 5 digit monitor display “CC”, the setting range is from 0.000A to 50.400A, and the setting interval of each setting knob and key is 0.0001A. Set STOP VOLT.V, the middle 5 digit monitor display “VOLT.V”, the lower 5 ...
OFF to 19999.9, and the setting interval of each setting knob and key is 0.1. 3-3. Initial setting of 3110 series load module The following tables detail the initial settings of the 3110 series of Load Modules when Shipped from the factory. Item...
3110 Series Operation Manual 51 Item Initial value Item Initial value CC L+Preset 0.0000 A V_Hi 81.000 V CC H+Preset 0.0000 A V_Lo 0.000 V CR H+Preset 68400 Ω I_Hi 70.200 A LIMIT CR L+Preset 68400 Ω I_Lo 0.00 A CV H+Preset 81.000 V...
52 PRODIGIT Item Initial value Item Initial value CC L+Preset 0.0000 A V_Hi 81.000 V CC H+Preset 0.0000 A V_Lo 0.000 V CR H+Preset 34200 Ω I_Hi 140.400 A LIMIT CR L+Preset 34200 Ω I_Lo 0.000 A CV H+Preset 81.000 V W_Hi 700.20 W...
3110 Series Operation Manual 53 3-4. Input terminal and wire consideration The Load input terminals are rated at 70A. Please note that the banana plug and spade/hook connectors provided in the accessory pack have a current rating of 20A. Please be sure to use the correct connection method if sinking high currents.
The OVP level is 105% of the 3110 nominal voltage rating. CAUTION: Never apply an AC voltage to the input of the 3110 series Load. Do not apply a DC voltage that is higher than 3110 Load Module’s rating. If this advice is ignored it is likely that damage will be caused to the electronic load module.
Page 63
If a reverse polarity situation occurs the load will sink power even if the LOAD button is OFF. No current will be displayed on the 3110 series load module. Current up to the load’s maximum current rating will be tolerated in reverse polarity. However there is no OVP OCP and OPP protection.
The interface allows the load settings to be configured remotely and measurements read back. There are two sets of programming terms for the 3110 series. One is referred to as the SIMPLE format and the other is COMPLEX format.
Page 65
3110 Series Operation Manual 57 Abbreviation Description Pin1 Carrier Detect Pin2 Receive Pin3 Transmit Pin4 Data Terminal Ready Pin5 Ground Pin6 Data Set Ready Pin7 Request To Send Pin8 Clear To Send Pin9 Ring Indicator PC RS232 Port...
LOW or HIGH as the command, it can choose only one as the setting command. Terminator:You have to send the program line terminator character after send the command, the available command terminator characters which can be accepted in 3110 Series mainframe is listed in Table 4-8. LF WITH EOI CR,LF...
3. The least significant number is the 3th behind the decimal point. 4.3110 series will set to the maximum value of the model automatically when the set RISE is over the specification of Load.
Page 76
2. The least significant number is the 5th behind the decimal point. 3. 3110 series will set to the maximum value of the model automatically when the value of Voltage which has been set is over the specification of Load.
Page 77
3110 Series Operation Manual 69 OCP: START Syntax : [PRESet:] OCP:START {SP}{NR2}{;NL} [PRESet:] OCP:START ? {;NL} Purpose : Set and read the initial value of OCP test Description : This command is used for setting the required initial value (I-START) of OCP test.
Page 78
70 PRODIGIT TCONFIG Syntax: [PRESet : ] TONFIG {NORMAL|OCP|OVP|OPP|SHORT}{;NL} [PRESet : ] TONFIG ? {;NL} Purpose : Set and read the function of Dynamic test Description : There are four options of this command. Those are NORMAL mode,OCP test ,OPP test and SHORT test.
Page 79
3110 Series Operation Manual 71 BATT: WH Syntax: [PRESet : ] BATT: WH {SP} {NR2} {; NL} [PRESet : ] BATT: WH? {; NL} Purpose: Set and read BATT WH Description: Set and read BATT WH. BATT: RTIME Syntax: [PRESet : ] BATT: RTIME? {; NL} Purpose: read BATT RTIME Description: read BATT RESULT TME.
Page 80
72 PRODIGIT SURGE: TIME Syntax [PRESet: ] SURGE: TIME {SP}{NR2}{; | NL} [PRESet: ] SURGE: TIME ?{; | NL} Purpose: Set and read the surge current test time. Description: This command is to set and read the surge current test time, SURGE TIME: 10~1000ms.
3110 Series Operation Manual 73 Purpose: To set the upper/lower limit value of threshold voltage. Description: This command is to set the upper/lower limit value of threshold voltage. When input voltage is lower than the lower limit value or higher than the upper limit value, NG indicating light will come on to indicate ”NO GOO”.
Page 82
[ STATe : ] CLR Syntax : [ STATe: ] CLR{;NL} Purpose : Clear the error flag of 3110 series which during the period of working Description : This command is for clearing the contents in the register of PROT and ERR.
? Syntax: [ STATe: ] PROTect?{;NL} Purpose: Query if there have protection flag which had been set in this 3110 series Description: 1.PROT? means the status of Protection of 3110 series. “1” means OPP occurred.”4”means OVP. “8” means OCP. Table 4-9 shows the corresponding number of protection status 2.Use command CLR to clear the register of PROT status to be “0”...
76 PRODIGIT 4.6.3. SYSTEM Set and Read the Status of 3110 [SYStem : ] RECall{ SP }m{ ,n } Syntax : [ SYStem : ] RECall{ SP }m{ ,n }{;NL} Purpose : Recall the status of Loading which had been saved in the Memory Description: This command is for recalling the status of Load which had been saved In the Memory .
Page 85
3110 Series Operation Manual 77 [SYStem : ] REMOTE Syntax : [SYStem : ] REMOTE { ; NL} Purpose : Command to enter the REMOTE status (only for RS232) Description:This command is for controlling the RS232 [SYStem : ] LOCAL Syntax : [SYStem : ] LOCAL { ;...
When connected in local sense mode the 5 digit voltage meter of the 3110 series Electronic load measures the voltage at its DC input terminals. The connecting leads between the DUT and the Electronic Load should be bundled or tie wrapped together to minimize inductance.
3110 Series Operation Manual 79 5-2. Remote sense connections Remote sensing compensates for the voltage drop in applications that require long lead lengths. It is useful under low voltage high current conditions. The remote voltage sense terminals (Vs+) and (Vs-) of the load are connected to (+) and (-) output of the DC Source.
80 PRODIGIT 5-3. Constant Current mode application The Constant Current (CC) mode is ideal for testing the Load Regulation, Cross Regulation, Output Voltage and Dynamic Regulation of the power supply under test. The CC mode can also be used to test the Discharge Characteristics and the Life Cycle of cells and battery packs.
3110 Series Operation Manual 81 5.3.2 Dynamic mode: The built-in pulse generators allow the user to recreate real world loads that vary With time Major application areas for dynamic operation in CC mode include: • Power supply load transient response testing •...
Page 90
82 PRODIGIT 5.3.3 CC Mode Operating Instructions Example: PSU 5 V / 3 A, CC mode, Level HI 3.000A, Level 1.500A 5.3.4.1 . These can be selected in turn by pressing the "MODE" key (8), LCD will illuminate According to the operating mode is selected CC.
This is because in CR mode the current and voltage ramp up together providing a ‘soft start’ when compared to standard CC mode. However please note that with the 3110 series of Electronic Loads allow an adjustable current ramp can be set. This feature is found within the dynamic settings as RISE slew rate.
84 PRODIGIT CURRENT SOURCE VOLTAGE SOURCE ELECTRONIC LOLAD ELECTRONIC LOLAD CR MODE CR MODE INPUT VOLTAGE LOAD RESISTANCE SETTING OUTPUT LOAD CURRENT Fig 5-5 Constant Resistance mode Application 5.4.2 CR Mode Operating Instructions Example: PSU 5 V / 3 A, CR mode, Level HI 2.0 Ohm, Level Lo 4.0 Ohm 5.4.2.1.
Page 93
3110 Series Operation Manual 85 5.4.2.2. Pressing the "Preset" Key (13) once will cause the button to illuminate. 5.4.2.2.1. Pressing the LEVEL key (12) LED once will illuminate, Select LEVEL Hi, Adjusted by the rotary knob and arrow key (21) can be read from the lower Display during Setting 2.0000Ω.
86 PRODIGIT 5-5. Constant Voltage mode application In Constant Voltage (CV) operation the load will attempt to sink as much current as required in order to reach the set voltage value. CV operation is useful in checking the load regulation of dc current sources. The CV mode is also ideal for characterizing the current limit of dc power supplies.
Page 95
3110 Series Operation Manual 87 5.5.3 CV Mode Operating Instructions Example: PSU 5 V / 1A, CV mode, Level HI 4.000V, Level 3.000V 5.5.3.1. These can be selected in turn by pressing the "MODE" key (8), LCD will illuminate According to the operating mode is selected CV.
(Fig 5-7b). Operating the 3110 series electronic load in CP mode is ideal for testing the characteristics of a battery. This is because as the battery voltage drops the load current will automatically increase in order to keep the CP setting.
3110 Series Operation Manual 89 (a) The output voltage of battery (b) The output current of battery (c) The output power of battery Battery Battery Plow Phigh (e) Constant Power Mode (DYNAMIC) (d) Constant Power Mode (STATIC) Fig 5-7 CONSTANT POWER MODE APPLICATION 5.6.2.
Page 98
90 PRODIGIT 5.6.2.2.2. Pressing the LEVEL key (12) LED once will illuminate, Select LEVEL Hi, Adjusted by the rotary knob and arrow key (21) can be read from the lower Display during Setting 5.000W. 5.6.2.3. Pressing the "Preset" Key (13) LED once will cause the button to off, Leave setting Mode.
3110 Series Operation Manual 91 5-7. Zero-Volt loading application As shown in Fig 5-8, the Electronic load can be connected in series with a DC voltage source which output voltage greater than 1V (3110, 3111, 3117), 6V (3114, 3119) or so that...
3110 Series Operation Manual 93 5-9. Power Supply OCP testing 5.9.1 OCP Manual control Example: 5.9.1.1. First, press Limit Key function to setting I_Hi 6A. 5.9.1.2. Press Limit Key function to setting I_Lo 0A. 5.9.1.3. Setting OCP test, press OCP key to the next step.
Page 102
94 PRODIGIT 5.9.1.7. Setting OCP VTH 0.600V, press OCP key to the next step. 5.9.1.8. Press START/STOP test key. 5.9.1.9. The UUT’s output voltage drop-out lower than the threshold voltage (V-th Setting), and the OCP trip point is between I_Hi and I_Lo limitation, then Middle 5 digits LCD display will shows "PASS", otherwise shows "FAIL".
3110 Series Operation Manual 95 5-10. Power Supply OPP testing 5.10.1 OPP Manual control Example: 5.10.1.1. First, press Limit Key function to setting W_Hi 30.00W.. 5.10.1.2. Press Limit Key function to setting W_Lo 0W.. 5.10.1.3. Setting OPP test, press OPP key to the next step.
96 PRODIGIT 5.10.1.7. Setting OPP VTH 0.600V,press OPP key to the next step. 5.10.1.8. Press START/STOP Test key. 5.10.1.9. the UUT’s output voltage drop-out lower than the threshold voltage (V-th setting), and the OPP trip point is between W_Hi and W_Lo limitation, then lower 5 digits LCD display will shows "PASS", otherwise shows "FAIL".
Page 105
3110 Series Operation Manual 97 SHORT Manual control Example 5.11.1.1. Setting SHORT test, press Short key to the next step. 5.11.1.2. Press UP key, setting Short time to 10000ms, press Short key to The next Step. 5.11.1.3. Press down key, setting V-Hi voltage to 1.000V, press Short key to the Next Step.
Page 106
98 PRODIGIT 5.11.1.6. Short test finish, the UUT’s drop voltage is between V_Hi and V_Lo limitation, then middle 5 digits LCD display will shows "PASS" 5.11.1.7. The UUT’s not drop voltage is between V_Hi and V_Lo limitation, LCD Display will shows FAIL.
Need help?
Do you have a question about the 3110 Series and is the answer not in the manual?
Questions and answers