(B) Heating - Sanyo SPW-XR253GH56 Technical Data & Service Manual

Table of Contents

Advertisement

(B) Heating

REMOTE CONTROL
SENSOR
(Only for wireless
remote controller)
SET. +1°C
SETTING TEMP.
SET. –1°C
BODY SENSOR
+1°C
SET TEMP.+4°C SHIFT
–1°C
SET TEMP.
OFF
COMPRESSOR
1
OUTDOOR FAN
OFF
(H, M or L)
2
OFF
INDOOR FAN
2
OFF
STANDBY
(31°C)
INDOOR HEAT
EXCH.
COIL
27°C
TEMP.
25°C
E2
SOLENOID
COIL (4-WAY)
TEMP.
OPERATION
OFF
BUTTON
Once the compressor starts, it keeps running for 5 minutes.
Once the compressor stops, it will not start running again for 3 minutes.
If you change the operation mode (HEAT, DRY, COOL or FAN) during the heating cycle,
the control circuit stops the compressor for 3 minutes.
For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off,
the compressor is not controlled by the room sensor.
When set on remote control sensor
Thermo ON: When room temperature is –1°C below the set temperature T˚.
Thermo OFF: When the room temperature is 1°C above the set temperature T˚, (T˚+1°C)
When set on body sensor
NOTE: In case of Body sensor, operating temperature is shifted to setting temperature +4°C .
THERMO. ON
THERMO. OFF
THERMO. OFF
THERMO. ON
5 MINUTES
3 MINUTES
ON
ON
3 SECONDS
SET SPEED
L
L
LL
ON
OFF
ON (REVERSING CYCLE)
1. Refer to 2-4 Outdoor Fan Speed Control
2. Refer to 2-2 Cold Draft Prevention (Heating)
Chart Summary and Explanations
Compressor
Compressor
II - 3
2. Processes and functions
THERMO. ON
THERMO. ON
MORE THAN
5 MINUTES
OFF
ON
OFF
ON
SET SPEED
LL
ON
OFF
ON
ON
OFF
THERMO. OFF
THERMO. ON
THERMO. OFF
THERMO. ON
MORE THAN
3 MINUTES
OFF
ON
OFF
ON
SET SPEED
LL
ON
OFF
1574_X_S
Fig. 2
SM830080
1
2
3
4
5