1-11 Installation Instructions
Electrical Characteristics
Indoor Unit : SPW-TR253GH56
Cooling
Performance at
A
Rating conditions
kW
A
Full load conditions
kW
Starting amperes
A
Heating (Heat pump only)
Performance at
A
Rating conditions
kW
A
Full load conditions
kW
Starting amperes
A
Cooling:
Rating Conditions
: Indoor Air Temperature
Full Load Conditions : Indoor Air Temperature
Heating:
Rating Conditions
: Indoor Air Temperature
Full Load Conditions : Indoor Air Temperature
Outdoor Unit : SPW-CR253GHL5
Indoor Unit
Fan Motor
Fan Motor
220 - 240 V / 1 phase / 50 Hz
0.43 / 0.43
0.62 / 0.65
90 / 100
0.13 / 0.15
0.43 / 0.43
0.62 / 0.65
90 / 100
0.13 / 0.15
1 / 1
Indoor Unit
Fan Motor
Fan Motor
220 - 240 V / 1 phase / 50 Hz
0.33 / 0.34
0.62 / 0.65
70 / 80
0.13 / 0.15
0.33 / 0.34
0.62 / 0.65
70 / 80
0.13 / 0.15
1 / 1
Outdoor Air Temperature 35°C DB
Outdoor Air Temperature 43°C DB
Outdoor Air Temperature
Outdoor Air Temperature 21°C DB / 15.5°C WB
I - 111
SPW-CR253GL5
Outdoor Unit
Compressor
380 - 415 V / 1 phase / 50 Hz
12.1 / 12.3
2.55 / 2.7
13.44 / 13.48
2.8 / 2.88
1 / 1
67 / 73
Outdoor Unit
Compressor
380 - 415 V / 1 phase / 50 Hz
13.7 / 13.5
2.86 / 2.96
15.6 / 15.2
3.25 / 3.29
1 / 1
67 / 73
27°C DB / 19°C WB
35°C DB / 23°C WB
20°C DB
7°C DB / 6°C WB
24°C DB
1. Specifications
Complete Unit
13.15 / 13.38
2.77 / 2.95
14.49 / 14.56
3.02 / 3.13
69 / 75
Complete Unit
14.65 / 14.49
3.06 / 3.19
16.55 / 16.19
3.45 / 3.52
69 / 75
SM830080