Sanyo SPW-XR253GH56 Technical Data & Service Manual page 37

Table of Contents

Advertisement

1-1 Unit Specifications
Concealed Duct Type
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity
Air circulation (Hi / Me / Lo)
Moisture removal (High)
External static pressure (High)
ELECTRICAL RATINGS
Voltage rating
Available voltage range
Running amperes*
Max. running amperes**
Power input
Power factor
C.O.P
Max. starting amperes
FEATURES
Controls / Thermostat control
Timer
Fan speeds Indoor / Outdoor
Airflow direction (Indoor)
Air filter
1
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation sound
Color (Approximate value)
1 2
REFRIGERANT TUBING
Limit of tubing length
Limit of tubing length at shipment
Limit of elevation difference
between the two units
Refrigerant tube
3
outer diameter
Refrigerant amount at shipment
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
4
Net weight
Shipping weight
Shipping volume
Cooling:
Rating conditions (*):
Full load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB
5
Heating:
Rating conditions (*):
Full load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB
Indoor Unit
Outdoor Unit
BTU / h
Liters/h
mmAq(Pa)
W / W
Indoor - Hi/Me/Lo
dB - A
Outdoor - Hi
dB - A
Indoor
Outdoor
m (ft.)
Narrow tube
mm (in.)
Wide tube
mm (in.)
Height
mm (in.)
Width
mm (in.)
Depth
mm (in.)
Height
mm (in.)
Width
mm (in.)
Depth
mm (in.)
kg (lb.)
kg (lb.)
m
3
Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DB
Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WB
SPW-UR363GHN56
SPW-CR363GHL8
380 - 400 - 415 V / 3N / 50 Hz
Cooling
kW
10.6
36,000
3
m
/h
1,800 / 1,560 / 1,260
4.2
8.1 (79) : at shipment, 12.4 (122) : using the booster cable
V
380
400
V
342 – 456
A
7.15
7.16
A
8.01
8.02
kW
4.03
4.09
%
85.6
82.5
2.63
2.59
A
47
49
Microprocessor / I.C. thermostat
ON / OFF 72-hours
3 and Automatic control / 2 (Auto)
Wired : RCS-SH80TG
Electronic expansion valve
Max. head 75 cm above unit bottom (25A, OD32 mm)
38 / 33 / 31, (42 / 38 / 33 : using the booster cable)
Munsell 5Y8.4 / 0.5, RAL 9002-GL
m (ft.)
m (ft.)
Outdoor unit is higher than indoor unit : 50 (164)
Outdoor unit is lower than indoor unit : 30 (98)
kg
Indoor unit
310 ( 12 - 7 / 32)
1,480 ( 58 - 9 / 32)
630 ( 24 - 26 / 32)
358 ( 14 - 3 / 32)
1,671 ( 65 - 25 / 32)
783 ( 30 - 26 / 32)
47 (104)
52 ( 115 )
(cu. ft)
0.468 (16.5)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
I - 32
1. Specifications
Heating
12.5
42,700
415
380
400
342 – 456
7.19
7.79
7.8
8.04
8.19
8.20
4.14
4.42
4.47
80.1
86.2
82.7
2.56
2.83
2.8
50
47
49
Field supply
Scroll (Sanyo)
53
50 (164 )
30 ( 98 )
9.52 (3 / 8)
19.05 (3 / 4)
R407C - 4.0
Outdoor unit
1,235 (48 - 20 / 32)
940 (37
340 (13 - 12 / 32)
1,326 (52 - 7 / 32)
1,016 (40
416 (16 - 12 / 32)
106 ( 234 )
113 ( 249 )
0.56 (19.8)
SM830080
415
7.83
8.23
4.50
80
2.78
50
)
)

Hide quick links: