10. Auto. Mode for Automatic Heating/Cooling Switching

COOLING SELECTION TEMP.
SHIFT SET TEMP.
REMOTE CONTROLLED
SHIFT SET TEMP.
HEATING SELECTION TEMP.
2
(1) This chart shows how the Operation Mode (COOLING or HEATING) is determined by the
(2) After operation starts, the set temperature shifts automatically by +2 deg. at cooling and by
(3) The change of the operation mode (heating to cooling, cooling to heating) by the change of
(4) In heating operation, using the body sensor, room temperature control is designed so that
(5) Within 10 minutes after the compressor turns OFF, the operation does not change to
(6) When switching from cooling (heating) to heating (cooling), the actuation of the 4 way valve
A
+2.5 deg
+2 deg
B
SET TEMP.
–2 deg
–3 deg
C
HEATING
Chart summary and Explanations
This control is effective only for one indoor unit or group control.
microprocessor taking the room temperature into consideration. It also shows the
temperature points at which the cooling or heating mode is switched, when the AUTO mode
is selected.
- 2 deg. at heating. For example, if cooling is selected, the set temperature changes from
20° C to 22° C.
(The display of the remote controller remains 20° C.)
the room temperature during the operation is as follows.
Heating to Cooling; Room temp. ≥ Shifted temp + 0.5 deg.
Cooling to Heating; Room temp. ≤ Shifted temp -1.0deg.
For example, if the room temperature rises above 22.5 °C (=22+0.5) during the cooling
operation at the room temperature 20° C set by the remote controller, the operation
changes to cooling. When the room temperature lowers below 17° C (=18-1.0) thereafter,
the operation changes to heating again.
room air temp. is sensed as 4 deg. lower than suctioned air at indoor unit taking into
account of the temperature gap between upper part and lower part of the room.
Accordingly, in this example, when the body sensor detection temperature reaches more
than 26.5 °C, the operation is changed from heating to cooling.
cooling (heating), even when the room temperature changes from C to A (A to C).
will delay about 30-50 seconds after the compressor turns ON.
COOLING
II - 10
Processes and Functions
HEATING
0440_M_S
SM830063