Sanyo SPW-XR253GH56 Technical Data & Service Manual page 115

Table of Contents

Advertisement

1-11 Installation Instructions
Electrical Characteristics
Indoor Unit : SPW-XR483GH56
Cooling
Performance at
Rating conditions
Full load conditions
Starting amperes
Heating (Heat pump only)
1
Performance at
Rating conditions
Full load conditions
1 2
Starting amperes
Cooling:
Rating Conditions
3
Full Load Conditions : Indoor Air Temperature
Heating:
Rating Conditions
4
Full Load Conditions : Indoor Air Temperature
5
Outdoor Unit : SPW-CR483GHL8
Indoor Unit
Fan Motor
220 - 240 V / 1 phase / 50 Hz
A
0.92 / 0.93
kW
200 / 220
A
0.92 / 0.93
kW
200 / 220
A
2 / 2
Indoor Unit
Fan Motor
220 - 240 V / 1 phase / 50 Hz
A
0.65 / 0.68
kW
140 / 160
A
0.65 / 0.68
kW
140 / 160
A
2 / 2
: Indoor Air Temperature
Outdoor Air Temperature 35°C DB
Outdoor Air Temperature 43°C DB
: Indoor Air Temperature
Outdoor Air Temperature
Outdoor Air Temperature 21°C DB / 15.5°C WB
SPW-CR483GL8
Outdoor Unit
Fan Motor
Compressor
380 - 415 V / 3 phase / 50 Hz
1.24 / 1.31
7.7 / 7.72
0.26 / 0.29
4.14 / 4.16
1.24 / 1.31
8.8 / 8.82
0.26 / 0.29
5 / 5.04
3 / 3
48 / 53
Outdoor Unit
Fan Motor
Compressor
380 - 415 V / 3 phase / 50 Hz
1.24 / 1.31
8.89 / 8.91
0.26 / 0.29
5.06 / 5.08
1.24 / 1.31
9.4 / 9.41
0.26 / 0.29
5.38 / 5.42
3 / 3
48 / 53
27°C DB / 19°C WB
35°C DB / 23°C WB
20°C DB
7°C DB / 6°C WB
24°C DB
I - 110
1. Specifications
Complete Unit
8.35 / 8.37
4.6 / 4.67
9.47 / 9.49
5.46 / 5.55
53 / 58
Complete Unit
9.48 / 9.52
5.46 / 5.53
9.99 / 10.02
5.78 / 5.87
53 / 58
SM830080