MACH® Series Gas-Fired Boiler
WARNING!
If overheating occurs or the gas supply fails to
shut off, do not turn off or disconnect the
electrical supply to the pump. Instead, shut off
the gas supply at a location external to the boiler.
4.3 T
B
O
YPICAL
OILER
Model
Input
Number
Rating
(Btu/hr)
300
300,000
450
450,000
Note: The heat exchanger is constructed and stamped for 50 psig maximum operating pressure and/or 200º F
maximum temperature.
C
PERATING
ONDITIONS
Natural Gas
*(1030 Btu/cu. ft.)
Gas Rate
Output
(CFH)
Capacity
(Btu/hr)
291*
275,000
437*
414,000
LP Gas
**(2500 Btu/cu. ft.)
Gas Rate
Output
(CFH)
Capacity
(Btu/hr)
120**
275,000
180**
414,000
Page 28
Operation
Total
Amperage
8 amps or less
8 amps or less