MACH® Series Gas-Fired Boiler
Parameter Settings for MCBA 14C 10XX Controls
No. Description
End User Settings
1
Setvalue for DHW
2
DHW system
3
CH system
4
Setpoint or Maximum Setpoint (OAR)
Service Settings
5
Minimum Setpoint, Outdoor Air Reset (OAR) 60 F
6
Minimum outdoor temp (OAR)
7
Maximum outdoor temp (OAR)
8
Frost protection, at OA Temp
9
Correction, Outdoor Air Sensor
10 CH shutdown setpoint temp (OAR)
11 Booster time
12 Outdoor Air Offset
13 Maximum fanspeed CH (hundreds)
14 Maximum fanspeed CH (units)
15 Maximum fanspeed DHW (hundreds)
16 Maximum fanspeed DHW (units)
17 Minimum fanspeed (hundreds)
18 Minimum fanspeed (units)
19 Ignition fanspeed (hundreds)
20 Postpumptime CH
21 Postpumptime DHW
22 CH modulation hysteresis On
23 CH modulation hysteresis Off
24 DHW modulation hysteresis On
25 DHW modulation hysteresis Off
Lower Limit
Upper Limit
Water Storage Tank: 68 F
Water Storage Tank: 158 F
0 = off
1 = on
2 = off+ pump continuous
3 = on+ pump continuous
0 = off
1 = on
2 = off+ pump continuous
3 = on+ pump continuous
68 F
182
140 F
-4 F
50 F
59 F
77 F
-22 F
50 F
-9 F
9 F
32 = off
34 F
140 F
0 = no booster
1 minute
30 minutes
0 F
144 F
10
70
00
99
10
70
00
99
5
70
00
99
5
70
0 = 10 Seconds
1 Minute
99 Minutes
0 Seconds
30 (*10.2 seconds)
0 F
36 F
0 F
18 F
-9 F
54 F
-9 F
54 F
Page 50
Appendix
MACH
MACH
Installed
300 PK
450 PK
MCBA
Factory
Factory
Parameter
Setting
Setting
Settings
for
for
MCBA
MCBA
14C1028
14C1036
NG
LPG
NG
LPG
140 140 140 140
0
0
0
0
1
1
1
1
180 180 180 180
80
80
80
80
20
20
20
20
70
70
70
70
32
32
32
32
0
0
0
0
32
32
32
32
0
0
0
0
0
0
0
0
60
57
56
54
00
00
00
00
60
57
56
54
00
00
00
00
16
20
12
20
00
00
00
00
35
35
25
25
1
1
1
1
3
3
3
3
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10