The information in this manual is the property of Patterson-Kelley. The descriptions and specifications contained in this manual were in effect at the time
this manual was approved for publication. While Patterson-Kelley will continue to support earlier model boilers to within a reasonable time limit, we
reserve the right to discontinue models and replacement parts at any time or change specifications or design without notice and without incurring any
GAS FIRED BOILERS
®
CONTROL SYSTEM
Natural Gas or Propane Gas
C-1500H/C-2000H
C-2500/C-3000/C-4000
Dual Fuel
C1500GG, C2000GG
C2500GG, C3000GG,
C4000GG
Part # 1004905981
C.S.A Design-Certified
Complies with ANSI Z21.13/CSA 4.9
Gas-Fired Low Pressure Steam and Hot Water Boilers
ASME Code, Section IV
Certified by Patterson-Kelley
C.S.A Design-Certified
Complies with ANSI Z21.13/CSA 4.9
Gas-Fired Low Pressure Steam and Hot Water Boilers
Summary of Contents for Patterson-Kelley MACH C-1500H
Page 1
Patterson-Kelley 2020: All Rights Reserved. The information in this manual is the property of Patterson-Kelley. The descriptions and specifications contained in this manual were in effect at the time this manual was approved for publication. While Patterson-Kelley will continue to support earlier model boilers to within a reasonable time limit, we reserve the right to discontinue models and replacement parts at any time or change specifications or design without notice and without incurring any obligation.
Page 2
® P-K MACH Gas Fired Boiler Technical Service 1.877.728.5351...
Page 3
® P-K MACH Gas Fired Boiler Technical Service 1.877.728.5351 Safety OTICE Each safety device must be & maintained and checked per the General recommended schedule. Refer to ® P-K MACH C-1500H, C-2000H, C-2500, C-3000, C-4000 Section for more information. ® All P-K MACH C-1500H, C-2000H, C-2500, C-3000, C-4000 Gas- AFETY...
Page 4
If any of the provisions of this manual are not fully and completely understood, contact Patterson-Kelley Technical Service at 570.476.7261 or toll free at 877.728.5351. Hazard Warnings...
Page 5
Collection and disposal must be in accordance with all applicable regulations. A condensate neutralization kit is available. Please contact your local Patterson-Kelley representative for more information. Burn, Fire and Explosion Hazards Burn, fire, and explosion hazards! Installation must be in strict conformance to all applicable codes and standards including NFPA 54, ANSI Z223.1 and CAN/CSA B.149.
3.5.5 Inlet Duct Connection to Boiler ..................34 3.5.6 Intake Duct Materials and Sizes ..................34 3.5.7 Category II Installations ....................35 3.5.8 Category IV Installations ....................36 Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Page 7
..............60 ORMAL IGHTING AND DOWN ROCEDURES 5.2.1 Normal Lighting Procedures ..................... 60 Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx Page 2...
Page 9
BOILERS IN MULTI-METAL SYSTEMS ................... 116 APPENDIX D – BEST PRACTICES FOR NEW & RETROFIT SYSTEMS ........117 APPENDIX E – INSTALLATION AND QUICK REFERENCE ............119 Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Patterson-Kelley cannot be responsible for the design or performance can be misused operation of such systems and a qualified engineer or contractor which could result in personal must be consulted.
Patterson-Kelley manufactures quality products. The primary concern of all Patterson-Kelley equipment installation procedures is Safety. Safety instructions and considerations are presented and repeated throughout the document as needed. At any time during the installation if you have any questions on the information contained within, or do not fully and completely understand the content, please contact Patterson-Kelley Technical Service at 570.476.7261 or toll free at 877.728.5351.
Insufficient clearance can restrict the service access, increasing the possibility of injury. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
(b) field installed gas cocks must be “T” handle type, (c) piping of condensate shall conform to the State Plumbing Code, and (d) refer to the Massachusetts Supplement for further details. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
NOTICE! This appliance is certified for INDOOR use only! The boiler must be level within 0.25° in order to function properly. Failure to heed this warning could result in personal injury or death. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Note: Failure to provide recommended service clearances may make it difficult to perform service on the boiler(s). Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Faulty vent installation can allow toxic fumes to be released into living areas. This may cause property damage, injury, or death. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
NOTE 2: When this material is used for venting, it must be listed to either UL- 1738 or ULC-S636 (depending on the local requirements). Consult the local boiler codes for more information. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Improper interconnection of venting systems may result in leakage of flue gases into occupied spaces. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Page 20
Section 3.5. The appliance connector should incorporate provisions to drain condensate formed in the vent system. The connector should include an appropriate drain section (not provided). Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
The P-K MACH proper water conditions to remain efficient and function properly. For more information, refer to Patterson-Kelley’s Water Quality Standards for Hydronic Boilers in Multi-Metal Systems in Appendix C – Water Quality Standards Quality Standards for Hydronic Boilers in Multi-Metal Systems as this applies to the warranty of your heat exchanger.
Gas Fired Boiler Technical Service 1.877.728.5351 3.2.1 Appliance Connections (C-1500H & C-2000H) All connections must be in compliance with national, state, and local code requirements. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Gas Fired Boiler Technical Service 1.877.728.5351 3.2.2 Appliance Connections (C-2500 & C-3000) All connections must be in compliance with national, state, and local code requirements. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Gas Fired Boiler Technical Service 1.877.728.5351 3.2.3 Appliance Connections (C-4000) All connections must be in compliance with national, state, and local code requirements. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
10AWG wire. Do not over-tighten the terminal screws. Maximum tightening torque = 6 in-lbs! Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
208 VAC main voltage. Refer to Section 7.1, for proper wiring and configuration of the internal control transformer. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Page 27
12 AWG wire. The ground terminal can accommodate Main Power Connection maximum 8 AWG wire. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
(DHW) Pump, Air Damper, System 240VAC and maximum current capacity of 1/2 Amp. Pump, etc. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Ground – TB1-17 provides an equipment (frame) ground connection for input, output, or communication connections. For independently powered control devices, it may be necessary to create a common ground. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Page 30
The wireless receiver should be installed at or near the boiler, and the wireless temperature sensor should be installed on the North face of the building and shielded from direct sunlight exposure. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
2. Screens shall be not smaller than 1/4 inch. 3. Motorized louvers shall be interlocked with the appliance so that they are proven open prior to main burner ignition and operation. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
F. When all combustion air is supplied through a make-up air heater, and the appliance is interlocked to the heater, the requirements of Paragraphs A through E do not apply. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
For example, joints in PVC or CPVC piping must be cemented. For galvanized duct, wrap each joint and seam with adhesive aluminum tape or other sealant. Patterson-Kelley recommends installing a 1” x 1” or larger bird screen on the exterior termination. Ensure that the screen does not become blocked with snow, ice, insects etc.
If the combustion air intake ductwork and the exhaust vent terminate on the same wall of NOTE: the building, they must utilize the same type of termination fitting. Patterson-Kelley recommends including a motorized combustion air damper in each NOTE: appliance’s air intake ductwork. Refer to Section 3.4.5...
Page 35
Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Vertical vents are allowed to be terminated with a variety of ends, including plain straight pipe, elbow, or vent tee. Horizontal vents must be terminated with an elbow or vent tee. Similarly, a bird screen with 1” x 1” openings is recommended for termination. Patterson-Kelley does not recommend using a vent rain cap of any type.
This is illustrated in the following diagram. Additionally, the boiler vent shall terminate at least 3 ft. above a forced air inlet located within 10 ft. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Patterson-Kelley recommends that common venting systems be designed for a maximum continuous exhaust pressure of -0.04” W.C. when measured in the common vent. Locking inline dampers are recommended on the exhaust connection of each individual appliance in order to control the exhaust back pressure within the appliance and upstream of this damper.
The installation of a 1” x 1” birdscreen on the intake termination is recommended. Ensure that the screen does not become blocked with snow, ice, insects, etc. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Category IV vent installations. 120VAC motorized dampers with end limit switches are available for purchase from Patterson-Kelley. Other damper motor voltages are acceptable, provided they do not exceed 240VAC. The Air Damper Interlock circuit for the end limit switch is always 120VAC which is sourced from the boiler itself.
3,000 cubic feet per 11 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or hour. CAN/CSA B149.1 Natural Gas and Propane Installation Code. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
If using soap and water or a similar leak test method, make sure to clean off all moisture from the gas pipe fittings prior to placing the appliance into service. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
All water connections should be in compliance with national, state, and local code requirements. Adapters from Victaulic to NPT are available from Patterson-Kelley. The bottom rear connection to the boiler is the INLET and must be used for the return from the system. The top rear connection to the boiler is the OUTLET and must be connected as the supply to the system.
Page 46
The condensate is acidic (pH between 3.0 and 5.0) and may be corrosive to some building drain systems. A condensate neutralization system may be required and is available from Patterson-Kelley. If the condensate drainage system is exposed to freezing temperatures, it must be field heat traced. The boiler could generate up to one gallon of condensate per 100,000 BTU input.
“water quality”. For information, can be found on our website www.pattersonkelley.com please refer to Patterson-Kelley Multi-Metal Systems Water Quality Standards as it appears in Appendix C – Water Quality Standards Quality Standards for Hydronic Boilers in Multi-Metal Systems as this applies to the warranty of your heat exchanger.
The manual reset high temperature limit is located inside the boiler’s front door, toward the top of the control panel and is identified with a yellow label. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
“Reset Control”. NOTE Make sure to re-open the downstream gas cock (inside the boiler) after a successful test. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
A combustion analyzer must be used. Combustion must be set in accordance with the Recommended Combustion Settings for P-K MACH Boilers in Section 3.11.2. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
NOTICE! For high altitude adjustments (greater than 2,000 feet above sea level), see Appendix B – Boiler Altitude Derate Schedule at the end of this manual. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
(units = V) as measured by the ignition electrode/ionization probe. When the boiler is in standby, prepurge, or postpurge the flame signal should read 0V. During main flame, a strong flame signal should read between 20-50V. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
When the boiler or water heater is powered on, the NURO touchscreen will display an initial Startup Screen then the Local Representative screen. This shows the name, address and phone number of the local Patterson-Kelley representative. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
NOTE For more information on any value, please refer to the NURO Boiler Controller: Advanced User’s Guide, Part Number is 1004905979. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Less than 20 3689 1600 3,800,000 C-4000 4,000,000 440-480 Three Less than 20 Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx Page 50...
4.4.3 for model-specific information on the location of the gas trains, the fuel selector switch and the dual fuel wiring diagrams. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
If operating with Natural Gas, ensure the Propane Gas valve/cock is CLOSED. If operating with Propane Gas, ensure the Natural Gas valve/cock is CLOSED. Failure to do so could result in equipment damage, injury, and/or death. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
If operating with Natural Gas, ensure the Propane Gas valve/cock is CLOSED. If operating with Propane Gas, ensure the Natural Gas valve/cock is CLOSED. Failure to do so could result in equipment damage, injury, and/or death. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
If operating with Natural Gas, ensure the Propane Gas valve/cock is CLOSED. If operating with Propane Gas, ensure the Natural Gas valve/cock is CLOSED. Failure to do so could result in equipment damage, injury, and/or death. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
If operating with Natural Gas, ensure the Propane Gas valve/cock is CLOSED. If operating with Propane Gas, ensure the Natural Gas valve/cock is CLOSED. Failure to do so could result in equipment damage, injury, and/or death. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
If operating with Natural Gas, ensure the Propane Gas valve/cock is CLOSED. If operating with Propane Gas, ensure the Natural Gas valve/cock is CLOSED. Failure to do so could result in equipment damage, injury, and/or death. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Natural Gas The boiler must be level within 0.25° in order to function properly. Failure to heed this warning could result in personal injury or death. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Gas Fired Boiler Technical Service 1.877.728.5351 4.5.2 High Turndown C1500T & C2000T Must be level for appliance to function correctly Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
A clear plastic cover protects the touch screen which can be opened by pinching the clasp and swinging open to the left. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
See illustration on the right for valve locations. The upper shut off valve is for Propane Gas and the lower valve for Natural Gas. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
NOTICE! Proper maintenance schedule and record this unit. Failure to do so could keeping is critical for optimum performance and to result in electrocution, injury, or maintain the Patterson-Kelley warranty. death. NOTE: The combustion blower motor is permanently lubricated and does not require periodic lubrication.
4. Replace the ignition electrode and gasket. 5. Drain and flush the water side of the heat exchanger as required (separate from system flush) using clean water only. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
11. Perform a leak test of the gas valves in accordance with the manufacturer's instructions. Cleaning the Burner & Combustion Chamber Patterson-Kelley recommends cleaning burner and combustion chamber once annually: 6.2.1 MACH C-1500H & C-2000H 1. Lockout/tagout gas supply to the boiler.
Page 69
Reseal the inspection cover and continue washing through the burner hole. 21. If the accumulation of debris on the fireside of the heat exchanger requires additional cleaning, use a serrated cleaning tool which is available from Patterson-Kelley. 22. Reconnect the condensate tubing to the condensate neutralization tank.
18. Move to the right hand side of the boiler, and remove one of the rectangular fireside inspection covers in the middle of the boiler by loosening the six M6 nuts. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Reseal the inspection cover and continue washing through the burner hole. 20. If the accumulation of debris on the fireside of the heat exchanger requires additional cleaning, serrated cleaning tool which is available from Patterson-Kelley. 21. Reconnect the condensate tubing to the condensate neutralization tank.
9. When the outlet water temperature is reduced by the load on the system, a heat request is generated. The operating sequence will recycle to Step 3. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Switch ON”, this indicates improper airflow through the boiler. First, verify proper standby blower operation – when the boiler is in “Standby”, the blower should also be in standby. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
When the blockage is removed, the boiler will automatically restart. If no blockage is found, it may be necessary to replace the high exhaust back pressure switch. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Gas Fired Boiler Technical Service 1.877.728.5351 7 Parts/Technical Support Spare parts and replacement parts can be ordered from Patterson-Kelley by calling toll free (877) 728-5351. Reach Use of Non-Factory Authorized us by fax at (570) 476-7247. replacement parts are not...
Page 76
® P-K MACH Gas Fired Boiler Technical Service 1.877.728.5351 Figure 7.1.1a Power Box Wiring Diagram (240V Configuration Shown) Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Page 77
® P-K MACH Gas Fired Boiler Technical Service 1.877.728.5351 Figure 7.1.1b Power Box Wiring Diagram (480V Configuration Shown) Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Configurable for Setpoint or Firing Rate Control ENABLE / DISABLE Contact Closure Enables Comfort Heat Operation Open Circuit Disables Comfort Heat Operation ENABLE / DISABLE Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
NEUTRAL N1 Unused Unused Unused L1 for 110-120VAC, Single phase, 60Hz HOT L1 Unused Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx Page 74...
P-K MACH Gas Fired Boiler Technical Service 1.877.728.5351 7.2.4 C2500 Wiring Diagram Patterson Kelley, LLC Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Page 87
® P-K MACH Gas Fired Boiler Technical Service 1.877.728.5351 Patterson Kelley, LLC Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx Page 82...
Improper configuration of the control transformer could result in serious injury or death. Figure 7.2.4a C-3000 & C-4000: 208 VAC, three phase, 60 hertz: Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Page 92
Technical Service 1.877.728.5351 Figure 7.2.4b C-3000 & C-4000: 220-240 VAC, Three Phase, 60 hertz: Figure 7.2.4c C-3000 & C-4000: 440-480 VAC, Three Phase, 60 hertz: Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Burner/Blower Assembly Front Door / NURO Touchscreen Cabinet Base Sheet Metal Cabinet Natural Gas Train Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
NURO Touchscreen Assembly Transformer XFMR1 (20VA) High Exhaust Back Pressure Switch Push to Test LWCO Button Air Pressure Switch Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Low Gas Pressure Switch Ignition Electrode & Gasket Internal (Downstream) Gas Cock Blower Gasket Air Intake Box & Transition Piece Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Main Gas Shutoff/Control Valve Combustion Blower / Fan Low Gas Pressure Switch Burner Transition Piece Air/Gas Venturi Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Gas Piping & Supports Main Gas Shutoff/Control Valve Low Gas Pressure Switch Internal (Downstream) Gas Cock High Gas Pressure Switch Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
NURO Control Panel Natural Gas Train Front Door / NURO Touchscreen Cabinet Base Sheet Metal Cabinet Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Grounding Terminal Blower Motor Relay 20A Three Phase Breaker (Incoming Three Phase Power) Fuse Holder Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Auxiliary High Exhaust Back Pressure (“Dirty Burner”) Combustion Blower / Fan Switch Burner Hood Casting High Gas Pressure Switch Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Stainless Steel Mesh Burner Combustion Blower / Fan Low Gas Pressure Switch Auxiliary High Exhaust Back Pressure (“Dirty Burner”) Switch Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx...
Page 115
Last Update 12/12/2016 Subject to the terms and conditions herein and the Terms and Conditions of Sale (as defined herein), Patterson-Kelley (“Seller”) warrants to the purchaser of the product (“Buyer”) that the heat exchanger and burner are free of defects in material and workmanship, when...
Page 116
No sales representative, agent, or employee of Seller or any reseller in the chain of sale of the product is authorized to make any modification, extension, or addition to this Specific Limited Warranty, unless agreed to in writing by Seller. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
® P-K MACH Gas Fired Boiler Technical Service 1.877.728.5351 8 Boiler Fire-Test Report Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx Page 112...
Page 118
® P-K MACH Gas Fired Boiler Technical Service 1.877.728.5351 Dual Fuel Addendum Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx Page 113...
Appendix A – Maintenance Log Hi Fire / Stack Date Action Low Fire Temp Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx Page 114...
Although the appliance’s capacity is reduced due to the lower air density, the combustion tuning should follow the standard combustion guidelines of Section 3.11.2. Tune the combustion for the same O levels as discussed in Section 3.11.2. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Gas Fired Boiler Technical Service 1.877.728.5351 Appendix C – Water Quality Standards Quality Standards for Hydronic Boilers in Multi-Metal Systems Patterson-Kelley boilers are designed to be incorporated into any multi-metal hydronic heating system. All multi- metal hydronic systems require that attention be paid to water treatment.
NOTE: This strainer is not intended to remove fine particulate matter from the boiler system which will be discussed later in this appendix. 4. Patterson-Kelley recommends installing a water meter on the cold water fill piping. The intention of this device is to periodically monitor the amount of fresh water introduced into the system piping.
Page 123
(blended) sample. 11. Within the first three months after startup, Patterson-Kelley recommends collecting a follow-up water sample from the hydronic system. This should be compared to the initial startup sample in order to determine any changes in pH, Alkalinity, conductivity, etc.
Maximum Inlet Pressure = 14.0” W.C. Maximum Inlet Pressure = 14.0” W.C. NOTE Patterson-Kelley recommends installing an individual lock-up type gas regulator in the gas supply piping to each boiler. For installations where one master lock-up type gas pressure regulator will service multiple...
Page 125
® P-K MACH Gas Fired Boiler Technical Service 1.877.728.5351 Appliance Connections (MACH C-1500H & C-2000H) All connections should be in compliance with national, state, and local code requirements. OTICE The appliance is furnished with a 3/4” manual drain (ball) valve which allows the user to completely drain the heat exchanger.
Page 126
The chart below represents the pressure drop (Ft of Head) versus the water flow rate (GPM) for the MACH C-1500H & C-2000H. This information is useful to help size an appropriate circulation pump. Keep in mind this pressure drop represents the boiler only, additional consideration is needed for any connected piping, valves, strainers, couplings, flanges, etc.
Page 127
The appliance is furnished with 3/4” drain tubing which is used to drain built-up condensation inside the appliance’s combustion chamber. Connect this 3/4” drain tubing to the condensate neutralization system. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Page 128
The appliance is furnished with 3/4” drain tubing which is used to drain built-up condensation inside the appliance’s combustion chamber. Connect this 3/4” drain tubing to the condensate neutralization system. Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved.
Page 129
Minimum Flow Ignition 95 GPM 40°F Minimum Flow Low Fire 76 GPM 20°F Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx Page 124...
Page 130
27.8 ft 425.6 GPM 19.7 ft 324.7 GPM 30.7 ft 447.2 GPM 21.7 ft Patterson-Kelley 2020 Revised: January 3, 2020 1004905981 P-K MACH C1500H-C4000 Installation and All Rights Reserved. Released: January 3, 2020 Owners Manual (Rev F Jan-2020).docx Page 125...