Page 1
MACH-04 C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers ASME Code, Section IV Certified by Patterson-Kelley C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers Installation Date: _______________________ 100 Burson Street, P.O.
MACH® Series Gas-Fired Boiler Table of Contents 1.0 INTRODUCTION ........1 3.6.11 Intake Duct Connection to Boiler ..12 3.6.12 Intake Duct Terminations ..... 12 2.0 SAFETY ............ 1 3.6.13 Vent Elbows ......... 13 2.1 General ..............1 3.7 Gas Piping ............13 2.2 Training..............1 3.7.1 Gas Supply Piping by Installer ....
Page 4
Failure to trained on the Patterson-Kelley MACH® Boiler. do so could result in fire or explosion and serious injury, death, and/or property damage.
Patterson-Kelley cannot be responsible Proper training is the best protection against accidents. for the design or operation of such systems and a Operating and service personnel must be thoroughly qualified engineer or contractor must be consulted.
Although the labels are of high quality, they NOTE may become dislodged or unreadable over time. When opening leak test valves, Contact Patterson-Kelley toll-free at (877) 728-5351 always follow instructions in operation and safety manual. for replacement labels. 1998 HCS, Inc. 800-748-0241 Reorder No.
MACH® Series Gas-Fired Boiler Safety • 2.5.3 Crush Hazards Burn hazard! Possible hot surfaces. Do not touch gas vent during firing operation. Use only factory recommended vent components. • Burn hazard! Pipes, vents, and boiler components could be hot. Do not touch piping or stack surfaces during operation or immediately after shutdown of the boiler.
MACH® Series Gas-Fired Boiler Safety 2.5.5 Pressure Hazards 2.5.6 Slip, Fall Hazards WARNING WARNING Improper use may Improper use may result in fire or injury. result in fire or injury. Read instructions/safety Read instructions/safety manual before installing, manual before installing, operating or servicing boiler.
MACH® Series Gas-Fired Boiler Installation 3.0 INSTALLATION Code, Section IV for 50 psig maximum operating pressure and/or 200º F maximum temperature. Other codes or approvals which apply will be labeled 3.1 R ECEIVING AND TORAGE on the boiler. Installation of the boiler must conform to all the requirements of all national, state and local codes 3.1.1 Initial Inspection established by the authorities having jurisdiction or,...
MACH® Series Gas-Fired Boiler Installation clearance and prevent distortion of the cabinet, (twisting, etc.) in addition to leveling. Adjustable Leg Bolts Minimum Clearances from Adjacent Walls, Ceiling, and Obstructions Type of Surface Dimensions (inches) Adjustable Legs for Leveling and Floor Clearance C†...
MACH® Series Gas-Fired Boiler Installation An external electrical disconnect (not supplied with when burned, form acids which quickly attack the the boiler) with adequate overload protection is boiler and the boiler stack. The result is improper required. The boiler must be grounded in accordance combustion and premature boiler failure.
MACH® Series Gas-Fired Boiler Installation If air is taken from another interior space, each 3.6.2 Flue Connection opening should have a net free area of 1 square inch The connection from the boiler to the vent should be for each 1,000 Btu per hour of boiler input (450 square as direct as possible and the upward slope of any inches for a 450,000 Btu per hour.) horizontal breaching should be at least 1/4 inch per...
MACH® Series Gas-Fired Boiler Installation 3.6.4 Vent Terminations WARNING! Do not locate intake or exhaust terminations directly above a walkway; dripping of conden- sation can cause icing of the walking surface. No rain cap or Tee. required, Mechanical draft vent terminal Direct vent terminal Outside Plate...
MACH® Series Gas-Fired Boiler Installation 3.6.6 Sealed Combustion Air/Venting System 3. Insofar as is practical, close all building doors and windows and all doors between the space in The MACH® Series Boilers are also certified for which the appliances remaining connected to the operation with a sealed combustion air and pressurized common venting system are located and other venting system.
Page 15
MACH® Series Gas-Fired Boiler Installation Exhaust Vent Exhaust Vent (type of (Type of flue termination flue termination optional when roof venting.) optional when roof venting.) Air Inlet (tee mounted horizontally.) Roof Air Inlet (Type of flue Roof termination optional.) Sidewall Sidewall Inlet, Roof Vent Roof Inlet and Vent Air Inlet...
MACH® Series Gas-Fired Boiler Installation 3.6.9 Intake Duct Materials and Sizes: Material: PVC, CPVC (Schedule 40), single wall Sidewall galvanized steel, or other suitable materials. Air Inlet The intake duct must be sized for a maximum pressure (tee mounted drop of 0.22 inches W.C., at 100 SCFM (MACH® horizontally) 450) or 70 SCFM (MACH®...
MACH® Series Gas-Fired Boiler Installation Remote Gas Shutoff 3.6.13 Vent Elbows (not supplied) The turn from horizontal to vertical should be made Natural Gas with two 45º ells or with one long radius 90º ell for Supply By Installer best operation. Do not use "short radius" ells. Union Drip Leg 3.7 G...
MACH® Series Gas-Fired Boiler Installation Pipe Capacity for Natural Gas Nominal Equivalent Pipe Length Maximum Capacity in Cubic Feet of Natural Gas per Hour Iron Pipe Internal Pressure Drop of 0.5 inch Water Column/Equivalent Length of Pipe (in feet) Size Diameter 90º...
Strainer Valve configured so as to limit the time rate of change of temperature at the boiler. Consult your authorized Patterson-Kelley boiler representative for application Boiler Inlet and Outlet Connections guidance. Make water connections as the application warrants, or at a minimum as shown, but always in compliance Piping With Air Handling Units with the local requirements.
MACH® Series Gas-Fired Boiler Installation 3.8.3 Boiler Water Piping by Installer Drain Valve and Piping A drain valve is installed in the inlet (system return) Strainer header connection to the boiler. Prior to draining the To avoid possible contamination of the boiler with boiler for maintenance or testing, electrical power and dirt, rust or sediment from the system, a strainer near gas supply must be turned off to the boiler.
MACH® Series Gas-Fired Boiler Installation untreated make-up water will cause premature failure IMPORTANT! due to buildup of scale; such failure is not covered by If the piping system attached to this unit will be warranty. chemically cleaned, the boiler must be Scale can also reduce efficiency.
MACH® Series Gas-Fired Boiler Installation 3.10 P TART HECK WARNING! Before attempting to start the boiler, make sure the following items have been completed. After checking controls by manual adjustment, make sure they are always reset to their proper 1. Section 3.9.1 Inspection. settings.
MACH® Series Gas-Fired Boiler Installation will occur. The LED indicator for Low Water cut-out 3.12 I NITIAL DJUSTMENTS will no longer be illuminated. Return the system to normal operation and restart the 3.12.1 Operating Temperature Controller for boiler. Refer to Section 4.2.1. MACH®...
Page 24
Turn the comfort heat system Parameters higher than 4 are only accessible by Plus long* on or off authorized service personnel trained on the P-K Show the domestic hot water MACH Series Boiler. Minus momentary setpoint Turn the domestic hot water Upper Minus...
Page 25
MACH® Series Gas-Fired Boiler Installation High Temp. Differential 0-36 Step Value Low Temp. Setpoint 59-140 Outlet water temp Inlet water temp Domestic Hot Water temp * The boiler will modulate to try to maintain 160° F. If the temperature increases above 169° F which is the Outdoor air temp * setpoint 160°...
Page 26
MACH® Series Gas-Fired Boiler Installation temperature controller indicates a call for heat from Outdoor Air Reset (optional): the DHW system. When the DHW system calls for heat, the Central heat pump output (Terminal 10 TB2) OU TD OO R A IR vs B OILER SETP O IN T deenergizes and the DHW pump output (Terminal 11 TB2) energizes providing 120 VAC power is provided to energize a relay coil for the DHW pump.
0-10 VDC signal. A signal of at least 0.5 VDC is Patterson-Kelley MACH® Series boiler. required to start the boiler. At 0 VDC the setpoint is 32° F; at 10 VDC the setpoint is 212° F. This setpoint...
MACH® Series Gas-Fired Boiler Installation Note: valve body for measuring supply pressure. (See figure Verify gas pressure at inlet to boiler is in below.) accordance with Table 3-1 below. Gas flow is dependent primarily on fan speed not upstream gas pressure.
Page 29
MACH® Series Gas-Fired Boiler Installation Table 3-1 Combustion Reading For Setting Gas Safety Shut Off / Control Valves Nominal High Fire Setting Low Fire Setting Model Fuel Gas Pressure % CO % CO Natural Gas 7" W.C. 4.9+ 0.2 9.1+ 0.2 5.1+ 0.2 8.9+ 0.2 7"...
Page 30
MACH® Series Gas-Fired Boiler Installation Low Fire Setting "R" Set boiler to the “Test Mode Low”, as described above, to achieve minimum firing rate of the boiler. Check combustion readings using a combustion analyzer. If combustion readings are not in accordance with Table 3-1 adjust as follows: •...
MACH® Series Gas-Fired Boiler Operation 4.0 OPERATION 4.2.1 Lighting Procedures 1. Close main gas valve. 4.1 G ENERAL 2. Turn On-Off switch to "OFF" position. 3. Wait 5 minutes. 4.1.1 Control Panel Front 4. Open main gas valve. 5. Turn On-Off switch to "ON" position. 6.
MACH® Series Gas-Fired Boiler Operation WARNING! If overheating occurs or the gas supply fails to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the boiler. 4.3 T YPICAL OILER...
5.1.1 Daily qualified installer or service agency who has been Observe operating temperature and general conditions. trained on the Patterson-Kelley MACH® boiler. Make sure that the flow of combustion and ventilating air to the boiler is not obstructed. Determine the cause of any service codes or lockouts on the display panel.
Installation and service must be performed by a with the manufacturer's instructions. qualified installer or service agency who has been trained on the Patterson-Kelley MACH® boiler. Installation and service must be performed by a The blower motor is permanently lubricated and does qualified installer or service agency who has been not require periodic lubrication.
MACH® Series Gas-Fired Boiler Maintenance 5.4 S 10. The unit modulates between the low fire setting EQUENCE OF PERATION and the high fire setting to maintain the desired outlet water temp set point. 1. When the On/Off (Main power) switch is turned on, power is provided through a circuit breaker to 11.
Page 36
MACH® Series Gas-Fired Boiler Maintenance Loss of Water Level High Water Temperature The low water switch opens when there is insufficient When the boiler water has exceeded both the operating water level in the boiler. E 12 is shown on the display, and high-limit temperature the high limit switch opens, and E 12 is shown on the display.
MACH® Series Gas-Fired Boiler Maintenance 5.5.1 Manual Reset Service Codes Code Lockout Description E 00 False flame. A flame signal is present when it shouldn’t be. E 02 Flame failure. The burner did not light on startup, or loss of flame during run. E 03 Gas Valve error.
MACH® Series Gas-Fired Boiler Maintenance 5.5.2 Auto-reset Service Codes Code Lockout Description b 08 Air pressure switch open. The air pressure switch failed to close to indicate sufficient air flow to start the boiler. b 18 Outlet high limit temp. The outlet water temperature has exceeded the internal high limit temperature setting.
6.0 PARTS/TECHNICAL SUPPORT Spare parts and replacement parts can be ordered from Technical information is also available at the above Patterson-Kelley by calling toll free (877) 728-5351. number. Ask for the Heat Transfer Department. The fax When ordering replacement parts please have the number is (570) 476-7247.
MACH® Series Gas-Fired Boiler Parts and Technical Support 6.1.1a Terminal Block Assignments – Low Voltage Circuit (TB1) Terminal Number Label Description HEAT REQUEST Boiler Enable, Contact Closure. DO NOT ENERGIZE. HEAT REQUEST INTERLOCK JUMPER External Limit (auto reset), Contact Closure. DO NOT ENERGIZE.
MACH® Series Gas-Fired Boiler Parts and Technical Support 6.2 B OILER ARTS 6.2.1 Main Assembly MACH Series 300 MACH Series 450 Mark Description Blower and Gas Train Manifold, System Return, Boiler Outlet Manifold, System Supply, Boiler Inlet Cabinet High Temperature - Aquastat...
MACH® Series Gas-Fired Boiler Parts and Technical Support 6.2.2 Control Panel Mark Description AM-3 Relay Module Boiler Control MACH Series - MCBA Transformer Low Water Cutoff Control Mounting Plate Page 41...
MACH® Series Gas-Fired Boiler Parts and Technical Support 6.2.3 Display Panel Mark Description Circuit Breaker Air Pressure Switch Fastening Clip Display Panel On/Off Switch Pressure Temperature Gauge Panel Sheet Metal Stack Pressure Switch Page 42...
MACH® Series Gas-Fired Boiler Parts and Technical Support 6.2.5 Series C-300 Boiler Gas Train Mark Description Main Gas Shut-off Valve Low Pressure Gas Switch Gas Safety Shut-off/Control Valve Air/Gas Manifold Swirlplate Blower Gas Leak Test Port Flex Hoses w/ Gas Valve Adaptors Page 45...
MACH® Series Gas-Fired Boiler Parts and Technical Support 6.2.6 Series C-450 Boiler Gas Train Mark Description Main Gas Shut-off Valve Low Pressure Gas Switch High Pressure Gas Switch Gas Safety Shut-off/Control Valve Gas Manifold Shut-off Valve Air/Gas Manifold Swirlplate Blower Gas Leak Test Port Flex Hoses with Gas Valve Adapters Page 46...
D. The design or operation of owner's plant or manufactured by Patterson-Kelley Co., Seller warrants equipment or of any facility or system of which to the original owner at the original installation site any Product may be made a part.
Page 52
MACH® Series Gas-Fired Boiler Limited Warranty charges to return the boiler and or components. SEVERABILITY Seller's liability under this warranty shall not in To the extent that any provision of this warranty would any case exceed the amount paid for the Product be void or prohibited under applicable law, such found to be defective.