LMACH- 07 PATTERSON-KELLEY MACH C1500/C2000 GAS-FIRED BOILER C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers ASME Code, Section IV Certified by Patterson-Kelley C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water...
Page 2
MACH® Series Gas-Fired Boiler Table of Contents...
MACH® Series Gas-Fired Boiler Table of Contents 1.0 INTRODUCTION ........1 3.6.12 Removing an Existing Boiler ....12 3.7 Gas Piping ............13 2.0 SAFETY............1 3.7.1 Gas Supply Piping by Installer ....15 2.1 General ..............1 3.8 Boiler Water Piping..........15 2.2 Training..............1 3.8.1 Piping Design .........15 2.3 Safety Features ..........2 3.8.2 Boiler Inlet and Outlet Connections ..
Page 4
The same features which permit this boiler to achieve trained on the Patterson-Kelley MACH Boiler. high-efficiency performance make it unlike most other boilers of this general size, so it is important to understand how this boiler operates.
Proper training is the best protection against accidents. Operating and service personnel must be 2.0 SAFETY thoroughly familiar with the basic construction of the P-K MACH C1500/C2000 boiler, the use and 2.1 G ENERAL locations of the controls, the operation of the boiler,...
Although the labels are of high quality, they When opening leak test valves, always follow instructions in may become dislodged or unreadable over time. operation and safety manual. Contact Patterson-Kelley toll-free at (877) 728-5351 1998 HCS, Inc. 800-748-0241 Reorder No. 8032-01NHPK for replacement labels. •...
MACH® Series Gas-Fired Boiler Installation • • Fire and explosion hazards! Do not store or use Overfire and underfire hazards! Possible fire, gasoline or other flammable vapors or liquids in explosion, overheating, and component failure. the vicinity of this or any other gas fired appliance. Do not attempt to adjust firing rate of the boiler.
MACH® Series Gas-Fired Boiler Installation 2.5.4 Chemical Hazards 2.5.6 Slip, Fall Hazards General Warning General Warning • Tripping hazard! Do not install piping on floor • Chemical hazards from cleaning products. Use surfaces. Maintain clear path around boiler. caution when cleaning the system. The use of •...
3.2 C OMPLIANCE WITH ODES The P-K MACH C1500/C2000 Boiler with standard Lifting the front of the boiler slightly will allow the components and options complies with American boiler to be rolled off the shipping skid onto the National Standard/CSA Standard ANSI Z21.13/CSA...
MACH® Series Gas-Fired Boiler Installation bolts may be removed allowing the wheels to recess up Minimum Clearances from Adjacent Walls, into the boiler. The base will sit flat on the provided Ceiling, and Obstructions (shown above &below) foundation. If the boiler is to be pulled out for maintenance, the wheels may be left attached.
MACH® Series Gas-Fired Boiler Installation requires less than 15 amps. Before starting the boiler, compounds, most commonly present as refrigerants check to ensure that the proper electrical service is or solvents, such as freon, trichlorethylene, connected to the boiler. perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the An external electrical disconnect (not supplied with boiler and the boiler stack.
MACH® Series Gas-Fired Boiler Installation • 3. Motorized louvers shall be interlocked with the When rooms are on different floors, each opening appliance so that they are proven open prior to shall have an area equal to 2 square inches for main burner ignition and operation.
MACH® Series Gas-Fired Boiler Installation Vent design calculations should be based on a This boiler should not be connected into any portion maximum of 0.44" W.C. combined frictional of another mechanical draft system without resistance across the air inlet duct and the stack, with a consulting your venting manufacturer.
To prevent the possible re-circulation of flue gases, the vent designer must take into consideration such things as prevailing winds, eddy zones, building configurations, etc. Patterson-Kelley Co. can not be responsible for the effects such adverse conditions may have on the operation of the boilers. Dimensions listed above or those illustrated are minimum, and may or may not be sufficient for conditions at a specific job site.
(1.22 m) horizontally from any electric of gas meter, regulator or relief equipment. 3.6.7 Sidewall Venting with Sealed Combustion The MACH C1500/C2000 Boilers are certified for direct sidewall venting with a sidewall air inlet only. Both the air inlet and the exhaust vent must terminate Vent Installation Details...
MACH® Series Gas-Fired Boiler Installation 3.6.8 Intake Duct Materials and Sizes: At the time of removal of an existing boiler, while the other appliances remaining connected to the common Material: PVC, CPVC, single wall galvanized steel, or venting system are not in operation, the following other suitable materials.
MACH® Series Gas-Fired Boiler Installation 3.7 G IPING RECOMMENDED GAS PIPING INSTALLATION Before making the gas hook-up, make sure the boiler is being supplied with the type of fuel shown on the Remote Gas boiler nameplate. Supply Shutoff The boiler shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance Drip Leg...
MACH® Series Gas-Fired Boiler Installation Pipe Capacity for Natural Gas Nominal Equivalent Pipe Length Maximum Capacity in Cubic Feet of Natural Gas per Hour Iron Pipe Internal Pressure Drop of 0.5 inch Water Column/Equivalent Length of Pipe (in feet) Size Diameter 90º...
Victaulic Style Couplings. These temperature at the boiler. Consult your authorized coupling must be used with the EPDM Victaulic Patterson-Kelley boiler representative for application seals. Adapters from Victaulic to NPT are guidance. available from the factory. Isolating valves must be installed in both water connections for ease of service.
Water Quality down and a flashing E 12 service code will be The MACH C1500/C2000 boiler heat exchanger is displayed on the control panel. The low water cutoff made of an aluminum alloy. The heat exchanger...
MACH® Series Gas-Fired Boiler Installation untreated make-up water may cause premature failure IMPORTANT! due to buildup of scale; such failure is not covered by warranty. If the piping system attached to this unit will be chemically cleaned, the boiler must be Scale can also reduce efficiency.
3.11.1 Test of Ignition Safety System resetting the boiler at the display panel. Readjust the MACH C1500/C2000 high-limit thermostat to the desired setpoint. Test the ignition system safety shutdown as follows: 3.11.4 Test of Gas Pressure Switch 1.
MACH® Series Gas-Fired Boiler Installation High Gas Pressure Switch The MACH® C1500/C2000 boiler is equipped with a The boiler is furnished with a high pressure switch that combination combustion and temperature control. must be checked by closing the downstream gas cock This control monitors combustion and lighting of the with the boiler off.
Page 24
MACH® Series Gas-Fired Boiler Installation Standby Mode: Parameter Mode: The display defaults to this mode at startup or reset of The parameter mode is used to change the settings of the control. If no key is pressed for 20 minutes the the boiler.
Page 25
MACH® Series Gas-Fired Boiler Installation The boiler will modulate to try to maintain 160° F. If Step Value the temperature increases above 169° F which is the Outlet water temp setpoint 160° F + High Temp Differential 9°F the Inlet water temp boiler will shut off.
Page 26
MACH® Series Gas-Fired Boiler Installation Outdoor Air Reset (optional): TB2) energizes providing 120 VAC power is provided to energize a relay coil for the DHW pump. The OU TD OO R A IR vs B OILER SETP O IN T DHW status should be set to 1 (DHW system ON).
MACH® Series Gas-Fired Boiler Installation above settings. Using the values in the table above, tables values are used the boiler setpoint will be 80° F the boiler setpoint will be 80° F when the outdoor air when the voltage is anything less than approximately 3 temperature is 70°...
MACH® Series Gas-Fired Boiler Installation adjusted to obtain proper combustion readings for specific local conditions. 3.12.3 Gas Pressure Adjustment Combustion measurement instrumentation must be Note: Adjustments shall only be performed by used to adjust the boiler for local conditions (See qualified and knowledgeable installer or service instructions below).
Page 29
MACH® Series Gas-Fired Boiler Installation Low Fire Setting Adjustment: Set boiler to the “Test Mode Low”, as described There must be sufficient load to operate the boiler at above, to achieve minimum firing rate of the boiler. high fire to perform the following adjustments. Check combustion readings using the combustion analyzer.
Page 30
MACH® Series Gas-Fired Boiler Installation C1500/C2000 Adjusting Low and High Analyzer probe in boiler exhaust High fire adjustment Low fire adjustment Table 3-1 Combustion Reading For Setting Gas Safety Shut Off / Control Valves Nominal High Fire Setting Low Fire Setting Fuel Gas Pressure % CO...
MACH® Series Gas-Fired Boiler Operation 4.0 OPERATION 4.2.1 Lighting Procedures 1. Close main gas valve. 4.1 G ENERAL 2. Turn On-Off switch to "OFF" position. 3. Wait 5 minutes. 4.1.1 Control Panel Front 4. Open main gas valve. 5. Turn On-Off switch to "ON" position. 6.
Page 32
MACH® Series Gas-Fired Boiler Operation 4.3 T YPICAL OILER PERATING ONDITIONS Model Input Total Natural Gas Number Rating Amperage (1030 Btu/cu. ft.*) (BTU/Hr) Gas Rate Output Capacity (CFH) (Btu/hr) C1500 1,500,000 Less than 15 1456* 1,440,000 C2000 2,000,000 Less than 15 1942* 1,920,000 Note: The heat exchanger is constructed and stamped...
Installation and service must be performed by a qualified and knowledgeable installer or service Observe operating temperature and general conditions. agency who has been trained on the Patterson-Kelley Make sure that the flow of combustion and ventilating MACH boilers. air to the boiler is not obstructed. Determine the cause of any service codes or lockouts on the display panel.
This procedure is qualified installer or service agency who has been available on request from the PK Factory. trained on the Patterson-Kelley MACH boiler. Installation and service must be performed by a The blower motor is permanently lubricated and does qualified installer or service agency who has been not require periodic lubrication.
MACH® Series Gas-Fired Boiler Maintenance 5.3 A FTER EPAIRS OR AINTENANCE 9. When the load is below the minimum firing rate of 1. Follow "Pre-Start Check List" (Section 3.10) and the boiler, the boiler will continue firing and the all "Safety Checks" (Section 3.11). outlet water temperature will rise until it reaches the set point + temperature differential.
MACH® Series Gas-Fired Boiler Maintenance 5.5 T ROUBLESHOOTING WARNING If any “Manual Reset” limit device trips, DO NOT reset without determining and correcting the cause. (Manual Reset Limits include: Flame safeguard, high or low gas pressure, high temperature limit) Loss of Water Level The MACH®...
Page 37
MACH® Series Gas-Fired Boiler Maintenance High Water Temperature When the boiler water has exceeded the high water temperature limit setting, the high limit switch opens Air Switch Closed and locks out. The control shows E 02 on the display. If the display panel indicates b 61, the air pressure When the water temperature falls below the high-limit switch did not open when the blower was shut off.
MACH® Series Gas-Fired Boiler Maintenance 5.5.1 Manual Reset Service Codes Code Lockout Description E 00 False flame. A flame signal is present when it shouldn’t be. E 02 Flame failure. The burner did not light on startup, or loss of flame during run or high temp limit tripped. E 03 Gas Valve Relay Board error.
MACH® Series Gas-Fired Boiler Maintenance 5.5.2 Auto-reset Service Codes Code Lockout Description b 08 Air pressure switch open. The air pressure switch failed to close to indicate sufficient air flow to start the boiler. b 24 Switched inlet / outlet. The inlet water temperature has been more than 18°...
Spare parts and replacement parts can be ordered from 6.1 S CHEMATIC IAGRAMS Patterson-Kelley by calling toll free (877) 728-5351. The fax number is (570) 476-7247. Refer to the parts list shown on the assembly drawing provided in this Typical schematic drawings are shown on the manual.
MACH® Series Gas-Fired Boiler Parts and Technical Support 6.2.1b Terminal Block Assignments – Low Voltage Circuit (TB1) Terminal Number Label Description HEAT REQUEST Boiler Enable, Contact Closure. DO NOT ENERGIZE. HEAT REQUEST INTERLOCK JUMPER External Limit (auto reset), Contact Closure. DO NOT ENERGIZE.
MACH® Series Gas-Fired Boiler Parts and Technical Support 6.3 B OILER ARTS 6.3.1 Main Assembly Mark Description Cabinet Top Boiler Outlet Boiler Inlet Blower/Burner Assembly Front Control Panel Cabinet Page 40...
MACH® Series Gas-Fired Boiler Parts and Technical Support 6.3.2 Control Panel Gas Valve Relay Board (GVRB) Mark Description Terminal Block 1 (TB1) 120V 120V/24V Transformer High Temperature Limit Low Water Cut Off (LWCO) Terminal Block 2 (TB2) Low V AM3 Relay Board Air Switch (on back) 10 Amp Circuit Breaker High Exhaust Back Pressure Switch...
MACH® Series Gas-Fired Boiler Parts and Technical Support 6.3.4 C1500/C2000 Gas Train Mark Description Burner Burner Gasket Blower Outlet Transition Piece Blower Outlet Gasket Blower Automatic Gas Valve Main Gas Shutoff Valve High & Low Gas Pressure Switches Secondary Manual Shutoff Vavle Gas Valve Sensing Line Venturi Page 43...
LIMITED WARRANTY with the unit Subject to the terms and conditions herein, Patterson-Kelley Co., 2. Adverse local conditions in general and, specifically, Seller, warrants to the original owner at the original installation site sediment or lime precipitation in the tubes and/or headers that products manufactured by Seller will be free from defects in or corrosive elements in the atmosphere.
Page 49
MACH® Series Gas-Fired Boiler Limited Warranty Page 45...
Page 50
MACH® Series Gas-Fired Boiler Appendix Page 46...