4.2.2 Normal Shut Down Procedures

1. Close all manual gas valves.
2. Turn off electric power.

4.2.3 Emergency Shut Off

Main and pilot gas cocks should be closed immedi-
ately if an emergency situation occurs; see Section
4.2.1 for the location of the gas cocks.
4.3 T
B
O
YPICAL
OILER
Model
Number
700
1000
1200
1500
max
min
1700
max
min
2000
max
min
C
PERATING
ONDITIONS
Input
Rating
(1030 Btu/cu. ft.)
(Btu/hr)
Gas Rate
(CFH)
700,000
680
1,000,000
971
1,200,000
1,165
1,500,000
1,456
900,000
874
1,700,000
1,650
1,020,000
990
2,000,000
1,942
1,200,000
1,165
If overheating occurs or the gas supply fails to shut
off, do not turn off or disconnect the electrical supply
to the pump. Instead, shut off the gas supply at a loca-
tion external to the boiler.
Natural Gas
Manifold
Output
Pressure*
Capacity
(in W.C.)
(Btu/hr)
1.4
595,000
1.9
850,000
2.4
1,020,000
2.2
1,275,000
765,000
1.7
1,445,000
867,000
2.3
1,700,000
1,020,000
Page 20
LP Gas
(2500 Btu/cu. ft.)
Gas
Manifold
Rate
Pressure*
Capacity
(CFH)
(in W.C.)
(Btu/hr)
278
3.5
397
4.4
476
4.2
1,044,000
595
2.8
1,305,000
357
674
2.1
1,479,000
404
793
2.7
1,740,000
476
1,044,000
Operation
Total
Amper-
age
Output
(amps)
609,000
8
870,000
8
9
12
783,000
12
12
887,400
12
12
12