MACH® Series Gas-Fired Boiler
6.1 W
D
IRING
IAGRAMS
6.1.1 Terminal Block Assignments – High Voltage Circuit (TB2)
Terminal Number
1
115 VAC LINE
2
115 VAC NEUTRAL
3
115 VAC NEUTRAL
4
115 VAC NEUTRAL
5
115 VAC NEUTRAL
6
GROUND
7
GROUND
8
GROUND
9
115 VAC SW. OUTPUT
10
115 VAC CIRC. PMP
CONTACTOR
11
115 VAC DHW PMP
CONTACTOR
12
MASTER ALARM RELAY
13
MASTER ALARM RELAY
14
THREE WAY VALVE RELAY
15
THREE WAY VALVE RELAY
16
DAMPER RELAY
17
DAMPER RELAY
Label
Boiler Supply Power, 115 VAC, 60 HZ, 1 ph, 8 amp
Aux. Switched Output
Boiler Circ. Pump
DHW Circ. Pump
Boiler Supply Ground
Aux .Ground
Aux. Switched Output, Pilot duty only, 1 amp max.
Boiler Circ. Pump, Pilot duty only, 1 amp max.
DHW Circ. Pump, Pilot Duty only, 1 amp max.
Dry Contacts, 24 VAC max, 1 amp max.
DHW Dry Contacts, 24 VAC max, 1 amp max.
Combustion Air Damper, Dry Contacts, 24 VAC max, 1 amp
max.