Clearances; Electrical Connections - Patterson-Kelley MACH Series Installation & Owner's Manual

Table of Contents

Advertisement

MACH® Series Gas-Fired Boiler
clearance and prevent distortion of the cabinet,
(twisting, etc.) in addition to leveling.
Adjustable Legs for Leveling and Floor Clearance

3.3.3 Clearances

If the boiler is to be installed near combustible
surfaces, the minimum clearances shown in the table
below must be maintained.
Failure to provide for the service access clearances,
even with non-combustible surfaces, may cause future
problems servicing the boiler.
The boiler must be installed in a space large in
comparison to the boiler as described in Section 6.3 of
the National Fuel Gas Code, ANSI Z223.1, latest
edition.
No pipes,
ducts, etc. in
this area.
A
Adjustable
Leg Bolts
C
B
Page 6
D
Minimum Clearances from Adjacent Walls, Ceiling, and
Type of Surface
Combustible Surfaces
Non-combustible Surfaces
† "C" Do not put pipes, ducts, etc. in this area above
the boiler.
CAUTION!
Bumping hazard from overhead ducts! Install all
components with adequate vertical clearances.
* Clearance depends upon vent configuration.
** Service access need be only on one side of a
boiler or row of boilers. Boilers may be installed
immediately adjacent to each other. However, P-K
recommends this clearance between each boiler
when there is insufficient access at the rear to allow
for service and adjustment.
3.4 E
C
LECTRICAL
ONNECTIONS
The boiler is wired for 120 volts, single phase, 60
hertz. The total operating amperage is indicated on
the rating nameplate. The 300 and 450 units require
less than 8 amps. Before starting the boiler, check to
ensure that the proper electrical service is connected
to the boiler.
Installation
D
Obstructions
Dimensions (inches)
A
B
C†
D
36
24
24
24
36
*
24
24**