MACH® Series Gas-Fired Boiler
No. Description
DHW 3 Way Vlv or Pmp (1st digit)
36 Manual fanspeed
37 PWM-level CH-pump:
38 Hold boiler water DHW only
39 Max Setpoint, 2nd CH-circuit
40 Min Setpoint, 2nd CH-circuit
41 Hysteresis 2nd CH-circuit
42 Low/off Cycle
Special pump CH / DHW
Lower Limit
Upper Limit
exchanger
X9 = External heat request (by RMCI )
0X = 3 way valve normally open
1X = Hot water pump
2X = 3 way valve normally closed
-1 = off
32 = off
34 F
176 F
50 F
176 F
50 F
140 F
34 F
86 F
X0 = Off
X1 = On
0X = CH: normal pump function
DHW: normal pump
function
1X = CH: pump off
DHW:normal pump function
2X = CH: normal pump function
DHW: 5 second pump delay
3X = CH: pump off
DHW: 5 second pump delay
Page 52
Appendix
MACH
MACH
Installed
300 PK
450 PK
MCBA
Factory
Factory
Parameter
Setting
Setting
Settings
for
for
MCBA
MCBA
14C1028
14C1036
NG
LPG
NG
LPG
X
X
X
X
-1
-1
-1
-1
41
41
41
41
32
32
32
32
100 100 100 100
50
50
50
50
14
14
14
14
00
00
00
00
X
X
X
X
X
X
X
X