Initial Start Up; Automatic Start Test; Manual Start Test - Eaton FD120 Manual

Diesel engine fire pump controllers
Table of Contents

Advertisement

O & M Manual IM05805019K-002
Effective April 2015
APPENDIX L: ALARM/STATUS MESSAGES (Continued)
Message
Description
Manual Mode
The controller is in Manual mode.
Manual Stop Request
The Stop pushbutton on the controller has been pressed
Menu Entered
The menu system was entered by a user
Off Mode
The controller is in Off mode
Pressure xxx PSI
System pressure readings the controller has recorded. Frequency adjusted via Pressure Deviation in the menu.
Pump Start
The pump has started via a pump start signal
Pump Start Off
The input to the Pump Start terminals has been removed
Remote Start
The pump has started via a remote start signal
RPT Timed Out
The running period timer has finished its timing cycle
RPT Stopped
The Run Period Timer has finished timing or been cleared.
Speed SW Malfunction
The engine run signal has been removed prior to the controller initiating a stop.
SST Started
The sequential start timer has started timing.
SST Stopped
The sequential start timer has finished timing or been cleared.
System Startup
Power has been reapplied to the system and a successful system boot has been completed
Transducer Fail
The controller has detected that the transducer has failed
Weekly Test Done
The weekly test has been completed
Weekly Test Fail
A Weekly test has been initiated, however the engine has failed to start.
Weekly Test Start
The engine has started on a weekly test
Weekly Test Stop
The Weekly Test Cycle timer has been cleared.

9. INITIAL START UP

Ensure that circuit breakers CB1 and CB2 are in the OFF (0)
position.
Ensure that AC power is supplied to terminals L and N, and G is
grounded.
Connect engine batteries to the controller, terminals 6, 8 and 11.
If batteries are connected in wrong polarity the battery voltage
will read zero.
Turn circuit breakers CB1 and CB2 ON ("1" position).
Pressure (start) is factory preset at 1 PSI.
Turn the mode selector switch to the "OFF" position
Ensure that the Diesel is programmed to user's specifications.
Refer to section 5 in this manual.

9.1 Automatic Start Test

Turn the mode selector switch to the "AUTO" position.
Ensure that water pressure is available and the LCD display on
the display panel is reading the system pressure correctly.
Decrease water pressure below the programmed start point.
The controller will begin its cranking cycle.
Should the engine fail to start after 6 crank and rest cycles, the
audible alarm will sound and the "Fail To Start" annunciator
will illuminate. Turning the mode selector switch to the "OFF"
position will silence the alarm.
When engine starts, "Engine Run" annunciator illuminates.
30
EATON INDUSTRIES CANADA COMPANY www.chfire.com
Diesel Engine Fire Pump Controller
Increase water pressure above programmed START point.
Press the stop pushbutton on the enclosure. If the pressure is
satisfied, and there are no other starting conditions the engine
will stop.
OR
If Auto Stop is programmed for "On", the engine will stop
automatically after the Run Period Timer times out and pressure
is satisfied. The RPT is programmed by the user; the factory
setting is 30 minutes.
If the Sequential Timer is > 0 seconds, automatic start will be
delayed by the number of seconds programmed.

9.2 Manual Start Test

Turn the mode selector switch to the "Manual" position
Press the Crank #1 pushbutton. The Engine will crank and start,
the "Engine Run" annunciator will illuminate.
Pres the STOP pushbutton. Wait for the engine to stop. Turn the
mode selector switch to the "Manual" position.
Press the Crank #2 pushbutton. The Engine will crank and start,
the "Engine Run" annunciator will illuminate.
Press the STOP pushbutton. The engine will stop. The engine
will stop.
EATON Diesel Plus