Controller Diagnostics; Communication; Usb; Information Download - Eaton FD120 Manual

Diesel engine fire pump controllers
Table of Contents

Advertisement

EATON Diesel Plus
Diesel Engine Fire Pump Controller
Table 5. Controller Statistics (Continued)
Statistic
Minimum Battery #1 Amperage
Minimum Battery #2 Amperage
Maximum Battery #1 Amperage
Maximum Battery #2 Amperage
Minimum System Pressure
Maximum System Pressure
Last System Startup
Last Engine Test
Last Low Oil Pressure
Last High Engine Temp.
Last Overspeed
Last Fail To Start
Last Low Fuel
Last Charger Failure
Last Battery Failure
Last ECM Alarm

6.3 Controller Diagnostics

The Diesel Plus controller has a number of diagnostic points
that can be used to help in troubleshooting issues with the
controller. The diagnostics can be viewed on the main display,
saved to a USB storage device, or viewed on the optional
embedded webpage.
In order to view the diagnostics on the display press the up or
down arrow buttons from the main screen until the display
shows "Controller Diagnostics" . Press the Ack. Alarm button to
view the diagnostics. The display will show the diagnostics. In
order to navigate the diagnostics use the up or down arrow
buttons.
The diagnostic information shall be provided to personnel trained in the
meaning of the values shown.
Diagnostic values that are recorded are the current date and
time, the microprocessor's firmware version, Eaton's shop
order number, customer order number, voltage readings,
pressure sensor readings, input status, and relay status.
Refer to Section 7 to save the controller diagnostics to a USB
storage device or to view the message history on the optional
embedded webpage.

7. COMMUNICATION

The Diesel Plus controller is available with a number of optional
communication protocols that can be used for the collection of
information.
Communication protocols include USB (standard), Ethernet and
RS485 (both optional).
Range
Unlimited
Unlimited
Unlimited
Unlimited
Unlimited
Unlimited
Date & Time
Date & Time
Date & Time
Date & Time
Date & Time
Date & Time
Date & Time
Date & Time
Date & Time
Date & Time
NOTE

7.1 USB

The USB port is used to download the controller message
history, statistics, diagnostics, status and configuration data to
a USB storage device. The USB port can also be used to upload
custom messages, additional languages, and update the
microprocessor firmware.

7.1.1 Information Download

• In order to download the history, diagnostics, statistics,
status and configuration - install a USB storage device into
the USB port on the display board. With the power on, press
the Data | Print button. The first selection is "Save to USB" .
Press the Ack. Alarm button and the controller will save the
information to the USB storage device.
• There will be five (5) files saved to the storage device. Refer to
Table 6 for the file nomenclature.
Table 6. File Nomenclature
File
ARC00000.csv
STC00000.txt
DIA00000.txt
STA00000.txt
CON00000.txt
• The .csv file is a comma separated values file that can be
opened using standard spreadsheet, word processor, or
database programs. The .txt files can be opened using
standard text viewers.

7.1.2 Custom Message Upload

• The Diesel Plus controller has the ability to store and use up
to ten (10) custom messages that can appear based on a
specific date, time, alarm or status condition.
• Refer to Appendix H to upload and enable the custom
messages.
• Refer to Section 8 for the creation of the custom message file.

7.1.3 Firmware Update

• Contact the factory or an authorized trained representative for
assistance.

7.1.4 Language Upload

• Contact the factory or an authorized trained representative for
assistance.

7.2 Embedded Webpage (Optional)

The controller is available with an optional webpage that can be
used to view the main display of the controller and its current
status.
Contact the factory or an authorized trained representative for
assistance in accessing the webpage.
EATON INDUSTRIES CANADA COMPANY www.chfire.com
O & M Manual IM05805019K-002
Nomenclature
Description
ARC=Archive
Message history
00000=Serial number
STC=Statistics
Controller statistics
00000=Serial number
DIA=Diagnostics
Controller diagnostics
00000=Serial number
STA=Statistics
Controller status
00000=Serial number
CON=Configuration
Controller configuration
00000=Serial number
Effective April 2015
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents