General Specification

Item
Model
NJ-PA3001
Supply voltage
100 to 240 VAC (wide-range), 50/60 Hz
Operating voltage and
85 to 264 VAC, 47 to 63 Hz
frequency ranges
Power consumption
120 VA max.
At 100 VAC:
20 A/8 ms max. for cold start at room temperature
*
Inrush current
1
At 200 VAC:
40 A/8 ms max. for cold start at room temperature
5 VDC, 6.0 A (including supply to CPU Unit using CPU Rack)
5 VDC, 6.0 A (using Expansion Rack)
*
Output capacity
2
24 VDC, 1.0 A
Total: 30 W max.
Output terminal
Not provided
(service supply)
Contact configuration: SPST-NO
*
RUN output
3
Switch capacity: 250 VAC, 2 A (resistive load)
120 VAC, 0.5 A (inductive load), 24 VDC, 2A (resistive load)
Replacement notification
Not provided
function
20 MΩ min.
*
Insulation resistance
4
(at 500 VDC) between AC external and GR terminals
2,300 VAC 50/60 Hz for 1 min between AC external and GR
Dielectric
terminals
*
*
strength
4
5
Leakage current: 10 mA max.
Noise immunity
2 kV on power supply line (Conforms to IEC 61000-4-4.)
5 to 8.4 Hz, 3.5-mm amplitude, 8.4 to 150 Hz, acceleration: 9.8 m/s
Vibration resistance
coefficient factor 10 = total time 100 min) (according to IEC 60068-2-6)
Shock resistance
147 m/s
Ambient operating
0 to 55°C
temperature
Ambient operating humidity
10% to 90% (with no condensation)
Atmosphere
Must be free from corrosive gases.
Ambient storage
-20 to 75°C
temperature
Less than 100 Ω
Grounding
Enclosure
Mounted in panel
Weight
470 g max.
174.7 to 484.7 × 90 × 90 mm (W × D × H) (not including cables)
CPU Rack dimensions
W = 70 (Power Supply Unit) + 90 (CPU Unit) + 20 × n + 31 × m + 14.7 (end cover)
n is the number of 32-point I/O Units or I/O Control Units and m is the number of other Units.
Safety measures
Conforms to cULus, EC Directives, NK and LR.
*
1. The AC and DC values above are given for a cold start, and the AC values are at room temperature. The AC inrush control circuit uses a
thermistor element with a low-temperature current control characteristic. If the ambient temperature is high or the Controller is hot-started, the
thermistor will not be sufficiently cool, and the inrush current given in the table may be exceeded by up to twice the given value. The DC inrush
control circuit uses a capacitor-charging delay circuit. If the power is OFF for only a short time for a hot-start, the capacitor will not sufficiently
discharge and the inrush current given in the table may be exceeded by up to twice the given value. An inrush current of approximately 4 A
may occur and continue for 1 s when the power is turned ON. When selecting fuses, breakers, and external DC power supply devices for
external circuits, allow sufficient margin in shut-off performance.
*
2. Internal components in the Power Supply Unit will deteriorate or be damaged if the Power Supply Unit is used for an extended period of time
exceeding the power supply output capacity or if the outputs are shorted.
*
3. Supported only when mounted to CPU Rack.
*
4. The tests can also be performed with the LG terminal and GR terminal connected to each other.
*
5. Change the applied voltage gradually using the adjuster on the Tester. If the full dielectric strength voltage is applied or turned OFF using the
switch on the Tester, the generated impulse voltage may damage the Power Supply Unit.
2
3 times each in X, Y, and Z directions (Relay Output Unit: 100 m/s
Specifications
NJ-PD3001
24 VDC
19.2 to 28.8 VDC
60 W max.
At 24 VDC:
30 A/20 ms max. for cold start
20 MΩ min.
(at 500 VDC) between DC external and GR terminals
1,000 VAC 50/60 Hz for 1 min between DC external and GR
terminals
Leakage current: 10 mA max.
2
in X, Y, and Z directions for 100 min (Time coefficient: 10 min ×
2
) (according to IEC 60068-2-27)
490 g max.
NJ-PA/PD