The pre-fab. module interior is decorated with B1 fire-resistant materials, and the
enclosure structure uses the 50 mm A1 fire-resistant rock wool material, providing a
fire resistance duration of 15 minutes. Requirements for higher fire resistance can be
met by customization, which will change the pre-fab. module and its interior structure.
NOTE
The pre-fab. module exterior can be protected with customized fireproof panels, which can
provide a fire resistance duration of 120 minutes as tested by the UL lab based on BS EN
1364-1:1999 and BS EN 1363-1:2012 standards.
The integrated cabling solution needs to be provided for project customization.
(Optional) IP55/IP65
Directly installed on the ground
NOTE
The pre-fab. module can also be installed on a concrete platform, with four 300 mm high steel
bases connected to the concrete platform using M16 bolts.
Preinstallation weight before delivery: ≤ 7500 kg; maximum load bearing capacity: ≤
10,000 kg
N63 cabinet: 600 x 300 x 2200 mm (air intake from front and air exhaust from top)
N66 cabinet: 600 x 600 x 2200 mm (air intake from front and rear, air exhaust from
top)
N68 cabinet: 600 x 800 x 2200 mm (air intake from front and air exhaust at rear)
–20°C to +55°C
NOTE
T ≤ 35°C: not derated. The maximum load rate decreases by 7.5% each time when the temperature
increases by 5°C.
–40 to +70°C
5%–95% RH
Class C environments, more than 500 m away from the seashore
Maximum altitude: 3000 m (derated when the altitude > 1000 m)
Altitude ≤ 1000 m: not derated. Working at an altitude of less than 1000 m, and
low pressure scenario are satisfied.
When the altitude exceeds 1000 m, the power of each 1000 m is derated by 5%.