FusionModule1000A20 Prefabricated All-in-One Data
Center
Product Description (380 V)
Item
tion
Surge
protection
level
Supported
device
power
Backup
time
Coolin
Cooling
g
capacity
Refrigerant
Temperatur
e control
range
Fire
Type
extingu
ishing
Alarm
Detection
Extinguisha
nt
Monito
IP camera
ring
Managemen
t function
Structu
Dimensions
re
(H x W x
D)
Thermal
Issue 01 (2019-10-31)
Specifications
380 V AC/400
380 V AC/400
V AC/415 V
V AC/415 V
AC, 50/60 Hz
AC, 50/60 Hz
Level 3 surge protection, nominal 20 kA (8/20 µs), maximum 40 kA (8/20 µs)
2N scenario: ≤
N+X scenario:
≤ 8 kW
8 kW
N+X scenario:
2N scenario: 6
2 hours (in the
hours (in the
initial state)
initial state)
8 kW (3+1 redundancy)
R134a
18°C to 30°C
Manual fire extinguishing in standard configuration, and automatic fire extinguishing
in the CE version.
(Optional) Automatic monitoring and detection, and the fire alarm horn/strobe is
supported.
(Optional) Gas is released when dual alarm conditions are met.
(Optional) Heptafluropropane.
Dual-resolution IP cameras installed at the main entrance door
Monitors the internal temperature, humidity control system, fire detection and control
system, access control system, cooling system, and power distribution system in real
time.
O&M using the mobile APP, remote unattended control
(Optional) Supports monitoring over emails and Simple Network Management
Protocol (SNMP) short messages.
All backup power sources are connected over programable dry contacts or fast
Ethernet (FE) ports.
20ft standard ISO shipping pre-fab. module: 2896 mm x 2438 mm x 6058 mm
Overall heat transfer coefficient of the pre-fab. module ≤ 0.59 W/(m
Copyright © Huawei Technologies Co., Ltd.
2 Typical Application Scenarios and Typical
380 V AC/400
380 V AC/400
V AC/415 V
V AC/415 V
AC, 50/60 Hz
AC, 50/60 Hz
2N scenario: ≤
N+X scenario:
≤ 16 kW
16 kW
N+X scenario:
2N scenario: 3
1 hour (in the
hours (in the
initial state)
initial state)
16 kW (4+1 redundancy)
Configuration
PE, 380 V
AC/400 V
AC/415 V
AC, 50
Hz/60 Hz
2N scenario:
≤ 24 kW
N+X
scenario: 3
hours (in the
initial state)
24 kW (2+1
redundancy)
R134a
18°C to
30°C
2
K)
8